| 2015-01-28 13:41:24 | 1/28/2015 |
| | PROJECT: KFC |
| | PERMIT#: 15010897 |
| | CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC |
| | ,2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1, |
| | ADMINISTRATION, 2012 FBC SUPPLEMENTS. |
| | 1ST ELECTRICAL PLAN REVIEW |
| | ACTION: DENIED |
| | |
| | REVISE PLANS IN RESPONSE TO THE FOLLOWING REVIEW |
| | COMMENTS: |
| | |
| | 1) SHEET T1.0 |
| | CHANGE THE VERSION OF THE NATIONAL ELECTRICAL CODE IN |
| | EFFECT AT THE TIME OF THIS SUBMITTAL FROM 2011 TO THE |
| | 2008 NEC. |
| | |
| | 2) SHEET E2.0 |
| | PROVIDE A GROUNDING ELECTRODE SYSTEM IN ACCORDANCE WITH |
| | NEC TABLE 250.66 FOR ELECTRICAL SYSTEM RISER. |
| | INDICATE THE CIRCUIT FEEDING PANEL LA. |
| | INDICATE THE FEEDER SIZE AND TYPE FEEDING PANEL LA. |
| | PROVIDE THE LOCATION OF THE ELECTRICAL SERVICE |
| | |
| | 3) SEPARATE PERMIT APPLICATIONS ACCOMPANIED BY |
| | MANUFACTURERS EQUIPMENT SUBMITTALS, AND SHOP DRAWINGS |
| | ARE REQUIRED FOR SITE LIGHTING, GENERATORS. HOOD |
| | EXHAUST, FIRE ALARM, ACCESS CONTROL SYSTEM, SECURITY, |
| | CCTV, AUDIO/VIDEO, NETWORK, DATA, AND, COMMUNICATION. |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. SEE LINK: |
| | HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/ |
| | 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF |
| | |
| | ADDITIONALLY, IT IS REQUIRED TO INSERT THE CORRECTED |
| | PAGES INTO THE DENIED SUBMITTAL PACKAGE. VOID THE |
| | PREVIOUSLY REVIEWED SHEETS AND LEAVE FOR COMPARATIVE |
| | REVIEW. |
| | |
| | DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421, |
| | 561-805-6717 OR [email protected] |
| | |