2015-01-28 13:41:241/28/2015
 PROJECT: KFC
 PERMIT#: 15010897
 CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC
 ,2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1,
 ADMINISTRATION, 2012 FBC SUPPLEMENTS.
 1ST ELECTRICAL PLAN REVIEW
 ACTION: DENIED
  
 REVISE PLANS IN RESPONSE TO THE FOLLOWING REVIEW
 COMMENTS:
  
 1) SHEET T1.0
 CHANGE THE VERSION OF THE NATIONAL ELECTRICAL CODE IN
 EFFECT AT THE TIME OF THIS SUBMITTAL FROM 2011 TO THE
 2008 NEC.
  
 2) SHEET E2.0
 PROVIDE A GROUNDING ELECTRODE SYSTEM IN ACCORDANCE WITH
 NEC TABLE 250.66 FOR ELECTRICAL SYSTEM RISER.
 INDICATE THE CIRCUIT FEEDING PANEL LA.
 INDICATE THE FEEDER SIZE AND TYPE FEEDING PANEL LA.
 PROVIDE THE LOCATION OF THE ELECTRICAL SERVICE
  
 3) SEPARATE PERMIT APPLICATIONS ACCOMPANIED BY
 MANUFACTURERS EQUIPMENT SUBMITTALS, AND SHOP DRAWINGS
 ARE REQUIRED FOR SITE LIGHTING, GENERATORS. HOOD
 EXHAUST, FIRE ALARM, ACCESS CONTROL SYSTEM, SECURITY,
 CCTV, AUDIO/VIDEO, NETWORK, DATA, AND, COMMUNICATION.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. SEE LINK:
 HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/
 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF
  
 ADDITIONALLY, IT IS REQUIRED TO INSERT THE CORRECTED
 PAGES INTO THE DENIED SUBMITTAL PACKAGE. VOID THE
 PREVIOUSLY REVIEWED SHEETS AND LEAVE FOR COMPARATIVE
 REVIEW.
  
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]
  