2015-03-02 11:43:043/2/2015
 PROJECT: 321 VALENCIA RD. ADDITION
 PERMIT#: 15010873
 CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC
 ,2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1,
 ADMINISTRATION, 2012 FBC SUPPLEMENTS.
 1ST ELECTRICAL PLAN REVIEW
 ACTION: APPROVED WITH EXCEPTION
  
 PROVIDE REVISED PLANS AND DOCUMENTATION ON SITE TO THE
 INSPECTOR AT THE FIRST INSPECTION TO INCLUDE THE
 FOLLOWING:
  
 1) NEC 230.70
 INDICATE THE LOCATION OF THE ELECTRICAL PANEL TO BE IN
 COMPLIANCE WITH THE NEC. 230.70
  
 2) 240.4, 240.24, 310.15(B)(6), 310.16
 A CODE COMPLIANT RISER DIAGRAM SHALL BE ON SITE FOR THE
 INSPECTOR TO INDICATE COMPLIANCE WITH NEC 240.4,
 240.24, 310.15(B)(6), AND 310.16
  
 3) NEC215.5
 PROVIDE A REVISED LOAD CALCULATION TO INDICATE THE
 ADDITION OF NEW LOADS.
  
 4) NEC 408.4
 PROVIDE A NEW PANEL SCHEDULE TO INDICATE THE ADDITION
 OF NEW LOADS.
  
 5) NEC 250.94
 PROVIDE AN INTERSYSTEM BOND STRIP AT THE ELECTRICAL
 SERVICE ON THE ELECTRICAL GROUNDING ELECTRODE.
  
 6) NEC 210.12
 PROVIDE ARC FAULT CIRCUIT PROTECTION ON ALL NEW
 CIRCUITS FOR THE NEW BEDROOM.
  
 7) NEC 406.11
 RECEPTACLES SHALL BE TAMPER RESISTANT.
  
 8) FBC-RESIDENTIAL 314 AND 315.
 PROVIDE SMOKE DETECTORS AS REQUIRED BYTHE FBC. VERIFY
 ALL SMOKE DETECTORS ARE INSTALLED AND INTERCONNECTED
 THROUGHOUT THE EXISTING RESIDENCE.
  
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]
  