| Date |
Text |
| 2015-03-02 11:43:04 | 3/2/2015 |
| | PROJECT: 321 VALENCIA RD. ADDITION |
| | PERMIT#: 15010873 |
| | CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC |
| | ,2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1, |
| | ADMINISTRATION, 2012 FBC SUPPLEMENTS. |
| | 1ST ELECTRICAL PLAN REVIEW |
| | ACTION: APPROVED WITH EXCEPTION |
| | |
| | PROVIDE REVISED PLANS AND DOCUMENTATION ON SITE TO THE |
| | INSPECTOR AT THE FIRST INSPECTION TO INCLUDE THE |
| | FOLLOWING: |
| | |
| | 1) NEC 230.70 |
| | INDICATE THE LOCATION OF THE ELECTRICAL PANEL TO BE IN |
| | COMPLIANCE WITH THE NEC. 230.70 |
| | |
| | 2) 240.4, 240.24, 310.15(B)(6), 310.16 |
| | A CODE COMPLIANT RISER DIAGRAM SHALL BE ON SITE FOR THE |
| | INSPECTOR TO INDICATE COMPLIANCE WITH NEC 240.4, |
| | 240.24, 310.15(B)(6), AND 310.16 |
| | |
| | 3) NEC215.5 |
| | PROVIDE A REVISED LOAD CALCULATION TO INDICATE THE |
| | ADDITION OF NEW LOADS. |
| | |
| | 4) NEC 408.4 |
| | PROVIDE A NEW PANEL SCHEDULE TO INDICATE THE ADDITION |
| | OF NEW LOADS. |
| | |
| | 5) NEC 250.94 |
| | PROVIDE AN INTERSYSTEM BOND STRIP AT THE ELECTRICAL |
| | SERVICE ON THE ELECTRICAL GROUNDING ELECTRODE. |
| | |
| | 6) NEC 210.12 |
| | PROVIDE ARC FAULT CIRCUIT PROTECTION ON ALL NEW |
| | CIRCUITS FOR THE NEW BEDROOM. |
| | |
| | 7) NEC 406.11 |
| | RECEPTACLES SHALL BE TAMPER RESISTANT. |
| | |
| | 8) FBC-RESIDENTIAL 314 AND 315. |
| | PROVIDE SMOKE DETECTORS AS REQUIRED BYTHE FBC. VERIFY |
| | ALL SMOKE DETECTORS ARE INSTALLED AND INTERCONNECTED |
| | THROUGHOUT THE EXISTING RESIDENCE. |
| | |
| | DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421, |
| | 561-805-6717 OR [email protected] |
| | |