| Plan Review Notes For Permit 15010861 |
| Permit Number |
15010861 |
|
| Review Stop |
B |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2015-05-21 08:22:38 | BUILDING REVIEW COMMENTS TO INFORMATION SUBMITTED TO | | | ADDRESS PREVIOUS PROVISO: | | | | | | THE ORIGINAL PROVISO COMMENT WAS: | | | | | | 1- REVISE RAS 117 CALCULATIONS: ARCHITECTURAL PLANS AND | | | NOA 12-0716.18 SUBMITTED CALL FOR INSULATED ROOF DECK. | | | CALCULATIONS SUBMITTED ARE FOR A NON INSULATED | | | ASSEMBLY. REVISE AS REQUIRED TO MATCH.. | | | | | | NOTE: THE PROVISO WAS TO REVISE THE RAS 117 | | | CALCULATIONS BECAUSE THEY DIDN'T MATCH THE SELECTED | | | ASSEMBLY TO BE INSTALLED. INFORMATION SUBMITTED WAS NOA | | | 12-0716.18 COVER PAGE AND PAGE 10 SHOWING THE INSULATED | | | ASSEMBLY. THIS INFORMATION WAS ALREADY SUBMITTED AND | | | APPROVED. WHAT WE NEED IS THE REVISED RAS 117 | | | CALCULATIONS TO MATCH THE SELECTED ASSEMBLY. REVISED | | | CALCULATIONS WERE NOT SUBMITTED. | | | | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT | | | JULIO GOMEZ | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | DEVELOPMENT SERVICES DEPARTMENT | | | (561)805-6712 | | | [email protected] |
|