| 2015-04-29 13:41:17 | 4/29/2015 |
| | PROJECT: PARK PL RESIDENTIAL RENOVATION |
| | PERMIT#: 15010861 |
| | CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC |
| | ,2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1, |
| | ADMINISTRATION, 2012 FBC SUPPLEMENTS. |
| | 1ST ELECTRICAL PLAN REVIEW |
| | ACTION: DENIED |
| | |
| | 1) PROVIDE THE LOCATION OF THE ELECTRICAL PANEL ON THE |
| | FLOOR PLAN. WPB AMENDMENTS OF THE FBC 107 |
| | |
| | 2) EVEN THOUGH THE FUEL SOURCE FOR THE WATER HEATER IS |
| | GAS THERE IS AN ELECTRICAL IGNIGHTER CIRCUIT THAT |
| | REQUIRES A DISCONNECT. PROVIDE THE LOCATION OF THE |
| | ELECTRICAL CIRCUIT AND DISCONNECT FOR THE ELECTRICAL |
| | WATER HEATER. NEC422.31 |
| | |
| | 3) INDICATE CIRCUIT NUMBERS ON THE FLOOR PLAN. VERIFY |
| | CIRCUITS IN THE DINING ROOM ARE 20AMP CIRCUITS. THERE |
| | ARE NO CIRCUITS IN THE PANEL CIRCUIT DIRECTORY |
| | INDICATED FOR THE DINING ROOM. WPB AMENDMENTS OF THE |
| | FBC 107 |
| | |
| | 4) INDICATE A SPECIFIC PURPOSE OR USE FOR EACH OF THE |
| | CIRCUITS IN THE PANEL CIRCUIT DIRECTORY. EVERY CIRCUIT |
| | AND CIRCUIT MODIFICATION SHALL BE LEGIBLY IDENTIFIED AS |
| | TO ITS CLEAR, EVIDENT, AND SPECIFIC PURPOSE OR USE. NEC |
| | 408.4 |
| | |
| | 5) VERIFY RECEPTACLE WALL SPACING. RECEPTACLES SHALL BE |
| | INSTALLED SUCH THAT NO POINT MEASURED HORIZONTALLY |
| | ALONG THE FLOOR LINE IN ANY WALL SPACE IS MORE THAN 1.8 |
| | M (6 FT) FROM A RECEPTACLE OUTLET. NEC 210.52 |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. SEE LINK: |
| | HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/ |
| | 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF |
| | |
| | ADDITIONALLY, IT IS REQUIRED TO INSERT THE CORRECTED |
| | PAGES INTO THE DENIED SUBMITTAL PACKAGE. VOID THE |
| | PREVIOUSLY REVIEWED SHEETS AND LEAVE FOR COMPARATIVE |
| | REVIEW. |
| | |
| | DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421, |