2015-03-06 09:01:43RESIDENTIAL (R3) ADDITION/ALTERATION MECHANICAL REVIEW
 COMMENTS.
 CODE: 2010 FBC.
  
 1- PROVIDE THE NAME AND COMPLETE INFORMATION OF THE
 DESIGN PROFESSIONAL WHO SIGNED AND SEALED THE M.1 SHEET
 AS REQUIRED BY CHAPTER 481 FLORIDA STATUTE.
  
 2- SHEET M.1: MASTER BEDROOM NEEDS TO COMPLY WITH THE
 BALANCED RETURN AIR SEC. M1602.4 OF 2010
 FBC-RESIDENTIAL. NOTE: TAKE INTO CONSIDERATION THAT ALL
 SUPPLY AIR INTO THE MASTER SUITE NEEDS TO BE CONSIDERED
 TO COMPLY WITH THE BALANCED RETURN AIR. THERE IS A
 TRANSFER GRILL LOCATED IN THE AHU #2 CLOSET. IF THIS
 GRILL IS FOR THE MASTER BEDROOM BALANCED RETURN AIR
 REQUIREMENTS, THEN IT DOESN'T COMPLY.
  
  