| Plan Review Notes For Permit 15010861 |
| Permit Number |
15010861 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2015-03-06 09:01:43 | RESIDENTIAL (R3) ADDITION/ALTERATION MECHANICAL REVIEW | | | COMMENTS. | | | CODE: 2010 FBC. | | | | | | 1- PROVIDE THE NAME AND COMPLETE INFORMATION OF THE | | | DESIGN PROFESSIONAL WHO SIGNED AND SEALED THE M.1 SHEET | | | AS REQUIRED BY CHAPTER 481 FLORIDA STATUTE. | | | | | | 2- SHEET M.1: MASTER BEDROOM NEEDS TO COMPLY WITH THE | | | BALANCED RETURN AIR SEC. M1602.4 OF 2010 | | | FBC-RESIDENTIAL. NOTE: TAKE INTO CONSIDERATION THAT ALL | | | SUPPLY AIR INTO THE MASTER SUITE NEEDS TO BE CONSIDERED | | | TO COMPLY WITH THE BALANCED RETURN AIR. THERE IS A | | | TRANSFER GRILL LOCATED IN THE AHU #2 CLOSET. IF THIS | | | GRILL IS FOR THE MASTER BEDROOM BALANCED RETURN AIR | | | REQUIREMENTS, THEN IT DOESN'T COMPLY. | | | | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT | | | JULIO GOMEZ | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | DEVELOPMENT SERVICES DEPARTMENT | | | (561)805-6712 | | | [email protected] |
|