 PROJECT: PARK PL RESIDENTIAL RENNOVATION
 PERMIT#: 15010861
 CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC
 ,2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1,
 ADMINISTRATION, 2012 FBC SUPPLEMENTS.
 1ST ELECTRICAL PLAN REVIEW
 ACTION:
  
 1) PROVIDE THE LOCATION OF THE ELECTRICAL SERVICE AND
 THE LOCATION OF THE ELECTRICAL PANEL ON THE FLOOR PLAN.
 WPB AMENDMENTS OF THE FBC 107
  
 2) PROVIDE THE LOCATION OF THE ELECTRICAL CIRCUIT AND
 DISCONNECT FOR THE ELECTRICAL WATER HEATER. NEC422.31
  
 3) REVISE THE WATER HEATER CIRCUIT TO INCLUDE THE
 CORECT OCPD AND WIRE SIZE. IF THE PROPOSED WATER HEATER
 IS 6KW THE CIRCUIT NEEDS TO BE UPDATED TO BE APPROVED A
 CONTINUOUS DUTY CIRCUIT RATED AT 125% OVER THE
 CONNECTED LOAD. NEC 422.13
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. SEE LINK:
 HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/
 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF
  
 ADDITIONALLY, IT IS REQUIRED TO INSERT THE CORRECTED
 PAGES INTO THE DENIED SUBMITTAL PACKAGE. VOID THE
 PREVIOUSLY REVIEWED SHEETS AND LEAVE FOR COMPARATIVE
 REVIEW.
  
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]
  