| 2015-03-06 09:38:36 | 3/6/2015 |
| | PROJECT: PARK PL RESIDENTIAL RENNOVATION |
| | PERMIT#: 15010861 |
| | CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC |
| | ,2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1, |
| | ADMINISTRATION, 2012 FBC SUPPLEMENTS. |
| | 1ST ELECTRICAL PLAN REVIEW |
| | ACTION: |
| | |
| | 1) PROVIDE THE LOCATION OF THE ELECTRICAL SERVICE AND |
| | THE LOCATION OF THE ELECTRICAL PANEL ON THE FLOOR PLAN. |
| | WPB AMENDMENTS OF THE FBC 107 |
| | |
| | 2) PROVIDE THE LOCATION OF THE ELECTRICAL CIRCUIT AND |
| | DISCONNECT FOR THE ELECTRICAL WATER HEATER. NEC422.31 |
| | |
| | 3) REVISE THE WATER HEATER CIRCUIT TO INCLUDE THE |
| | CORECT OCPD AND WIRE SIZE. IF THE PROPOSED WATER HEATER |
| | IS 6KW THE CIRCUIT NEEDS TO BE UPDATED TO BE APPROVED A |
| | CONTINUOUS DUTY CIRCUIT RATED AT 125% OVER THE |
| | CONNECTED LOAD. NEC 422.13 |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. SEE LINK: |
| | HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/ |
| | 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF |
| | |
| | ADDITIONALLY, IT IS REQUIRED TO INSERT THE CORRECTED |
| | PAGES INTO THE DENIED SUBMITTAL PACKAGE. VOID THE |
| | PREVIOUSLY REVIEWED SHEETS AND LEAVE FOR COMPARATIVE |
| | REVIEW. |
| | |
| | DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421, |
| | 561-805-6717 OR [email protected] |
| | |