| 2015-03-05 16:02:03 | RESIDENTIAL (R3) ADDITION/ALTERATION BUILDING REVIEW |
| | COMMENTS. |
| | CODE: 2010 FBC. |
| | |
| | 1- BRING PLANS TO PALM BEACH COUNTY (2300 N. JOG RD) |
| | FOR IMPACT FEES ASSESSMENT. BRING BACK COUNTY STAMPED |
| | PLANS AND COPY OF PAID RECEIPT IF FEES ARE DUE. COUNTY |
| | IMPACT FEE ORDINANCE OF THE UNIFIED LAND DEVELOPMENT |
| | CODE. |
| | |
| | 2- VALUATION DECLARED IN THE PERMIT APPLICATION WAS TOO |
| | LOW. VALUATION TO INCLUDE ALL LABOR, MATERIALS, |
| | CONTRACTOR'S OVERHEAD AND PROFIT AND DESIGN |
| | PROFESSIONAL FEES. VALUATION BASED ON ALL SCOPE OF WORK |
| | SHOWN ON PLANS WAS UPDATED TO $120,000 MIN. THE PERMIT |
| | FEE BALANCE IS $2528.70. |
| | |
| | 3- PROVIDE MANUFACTURER'S CUT SHEETS FOR 24EH SINGLE |
| | HUNG WINDOWS TO VERIFY COMPLIANCE WITH EGRESS |
| | REQUIREMENTS OF SEC. R310 OF 2010 FBC-RESIDENTIAL. |
| | (NOTE: ALSO SEE HISTORIC REVIEW COMMENTS REGARDING SIZE |
| | OF WINDOWS). |
| | |
| | 4- DESIGN CRITERIA ON SHEET SP-1 AND SHEET S-000 |
| | DOESN'T MATCH. EXPOSURE CATEGORY IS DIFFERENT. REVISE |
| | AS REQUIRED TO MATCH. |
| | |
| | 5- COMPONENTS AND CLADDING ON SHEET S-000: ACCORDING TO |
| | FOOTNOTE ON FIGURE R301.2(7) THE MIN. DIMENSION FOR |
| | ZONE #3 IS 4'-0". REVISE THE "A" DISTANCE ON NOTE #2 OF |
| | DETAIL A ON SHEET S-000. |
| | |
| | 6- ENERGY CALCULATIONS: REVISE DOORS INFORMATION. THERE |
| | ARE NOT WOOD DOORS. SEE PLANS AND PRODUCT APPROVALS |
| | SUBMITTED. SEC. 103.2.2 OF 2010 FBC-ENERGY |
| | CONSERVATION. |
| | |
| | 7- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY |
| | DCA RULE 9N-3 FOR: |
| | A) WINDOW MULLIONS. NOA 11-0922.01 SUBMITTED WAS |
| | SUPERSEDED BY MIAMI-DADE. PROVIDE CURRENT NOA. |
| | |
| | B) ROOF TILE ADHESIVE. NOA 12-0228.18 SUBMITTED WAS |
| | SUPERSEDED BY MIAMI-DADE. PROVIDE CURRENT NOA. |
| | |
| | C) SIMPSON HGAM10 STRUCTURAL CONNECTOR. JAX APEX |
| | TECHNOLOGY REPORT SUBMITTED IS NOT AN APPROVED PRODUCT |
| | APPROVAL. MANUFACTURER MAY APPLY FOR LOCAL PRODUCT |
| | APPROVAL IF THERE IS NOT AN OFFICIAL PRODUCT APPROVAL. |
| | |
| | D) TAMKO MODIFIED BITUMEN ROOF SYSTEM NOA 12-0716.18 |
| | WAS SUPERSEDED BY MIAMI-DADE. PROVIDE CURRENT NOA. |
| | |
| | E) ENTRY DOOR AS SHOWN ON PLANS. |
| | |
| | 8- DESIGNER OF RECORD TO APPROVE PRODUCT APPROVALS AS |
| | REQUIRED BY SEC. 107.3.4.1 OF CITY AMENDMENTS TO FBC. |
| | NOTE: PLEASE STAMP REVIEW STAMP ON FRONT OF PRODUCT |
| | APPROVAL PAGE NOT ON THE BACK. THIS IS REQUIRED FOR THE |
| | PROPER RECORDS RETENTION SCANNING PROCESS. |
| | |
| | 9- CLAY TILE NOA 12-0529.12 SUBMITTED DOESN'T SHOW ANY |
| | FASTENING SYSTEM USING #10 SCREWS. ARCHITECT TO REVISE |
| | ALL DETAILS AND SPECIFICATIONS ON PLANS TO MATCH |
| | PRODUCT APPROVAL OR PROVIDE A DIFFERENT CLAY TILE NOA |
| | THAT ALLOWS NAILS. SEC. R301 OF 2010 FBC-RESIDENTIAL. |
| | AND SEC. 107.2.1.2 CITY AMENDMENTS. |
| | |
| | 10- TAMKO MODIFIED BITUMEN ROOF SYSTEM: PROVIDE SIGNED |
| | AND SEALED RAS 117 CALCULATIONS AS REQUIRED BY GENERAL |
| | LIMITATION #7 OF TAMKO NOA SUBMITTED. CALCULATIONS |
| | REQUIRED TO MEET THE DESIGN PRESSURES REQUIRED BY SEC. |
| | R301 OF 2010 FBC-RESIDENTIAL. |
| | |
| | **** PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH |
| | COMMENT TO EXPEDITE THE REVIEW PROCESS. |
| | **** PLEASE REPLACE AND REMOVE ANY REVISED DRAWING. |
| | |