2015-05-12 11:47:1415010809
 1813 TAMARIND AVE.
 RESIDENTIAL RENOVATION
 2ND REVIEW
  
 PLEASE REVISE THE PLANS IN RESPONSE TO THE ELECTRICAL
 REVIEW COMMENTS. SEVERAL OF THE INITIAL RESPONSES TO
 THE LAST REVIEW WERE INCOMPLETE AND REQUIRE
 CLARIFICATION OR ADDITIONAL INFORMATION.
  
 INCLUDE AN ELECTRICAL LOAD CALCULATION FOR THE SERVICE
 FEEDING THE BUILDING. MAIN DISCONNECTS ARE REQUIRED TO
 BE GROUPED IN ONE LOCATION. SHOW THE SIZE OF EACH
 SERVICE AND EACH MAIN DISCONNECT. NEC 230.2 NEC 110.20,
 230.66, 230.79, 230.71
  
 A BUILDING WHICH HAS MULTIPLE ELECTRIC SERVICES MUST
 HAVE ALL GROUNDING ELECTRODE CONDUCTORS BONDED
 TOGETHER. PROVIDE A GROUNDING AND BONDING DETAIL. NEC
 250.58
  
 PROVIDE A MAIN BONDING STRIP AT THE ELECTRIC SERVICE
 GROUND. NEC 250.94
  
 INDICATE THE FAULT CURRENT CAPACITY REQUIRED FOR THE
 ELECTRIC SERVICE AND ELECTRIC PANELS. NEC 110.9, 110.10
  
  
 ROBERT LECKY
 ELECTRICAL PLANS EXAMINE
  