| Plan Review Notes For Permit 15010809 |
| Permit Number |
15010809 |
|
| Review Stop |
E |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2015-05-12 11:47:14 | 15010809 | | | 1813 TAMARIND AVE. | | | RESIDENTIAL RENOVATION | | | 2ND REVIEW | | | | | | PLEASE REVISE THE PLANS IN RESPONSE TO THE ELECTRICAL | | | REVIEW COMMENTS. SEVERAL OF THE INITIAL RESPONSES TO | | | THE LAST REVIEW WERE INCOMPLETE AND REQUIRE | | | CLARIFICATION OR ADDITIONAL INFORMATION. | | | | | | INCLUDE AN ELECTRICAL LOAD CALCULATION FOR THE SERVICE | | | FEEDING THE BUILDING. MAIN DISCONNECTS ARE REQUIRED TO | | | BE GROUPED IN ONE LOCATION. SHOW THE SIZE OF EACH | | | SERVICE AND EACH MAIN DISCONNECT. NEC 230.2 NEC 110.20, | | | 230.66, 230.79, 230.71 | | | | | | A BUILDING WHICH HAS MULTIPLE ELECTRIC SERVICES MUST | | | HAVE ALL GROUNDING ELECTRODE CONDUCTORS BONDED | | | TOGETHER. PROVIDE A GROUNDING AND BONDING DETAIL. NEC | | | 250.58 | | | | | | PROVIDE A MAIN BONDING STRIP AT THE ELECTRIC SERVICE | | | GROUND. NEC 250.94 | | | | | | INDICATE THE FAULT CURRENT CAPACITY REQUIRED FOR THE | | | ELECTRIC SERVICE AND ELECTRIC PANELS. NEC 110.9, 110.10 | | | | | | | | | ROBERT LECKY | | | ELECTRICAL PLANS EXAMINE | | | |
|