| 2015-04-30 07:03:23 | BUILDING PLAN REVIEW |
| | PERMIT: 15010809 |
| | ADD: 1813 N. TAMARIND AVE. |
| | CONT: FIC CONSTRUCTION |
| | TEL: (407)744-5664 |
| | |
| | 2010 FLORIDA BUILDING CODE W |
| | * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION |
| | 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. |
| | |
| | 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| | OF THE FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 3RD REVIEW |
| | DATE: THURS. APRIL 30/ 2015 |
| | |
| | NOTICE !!!!!!!!!!!!!NOTICE!!!!!!!!!!!!!!: CHAPTER |
| | 553.80(2)(B) FLORIDA STATUTES STATES THAT A LOCAL |
| | GOVERNMENT SHALL IMPOSE A FEE OF FOUR TIMES THE FEE FOR |
| | PLAN REVIEW, IF PLANS ARE REJECTED (3) OR MORE TIMES |
| | FOR REPEATED FAILURE TO CORRECT A CODE VIOLATION. |
| | ------------------------------------------------------- |
| | ------------------------------------------------------- |
| | ------------------------------------------------------- |
| | ------------------------------------------------------- |
| | ---------------------------- |
| | ACTION: DENIED |
| | |
| | 1) COMPLIED. SINGLE FAMILY DWELLING UNIT. PARTIAL |
| | CHANGE OF OCCUPANCY. |
| | |
| | 2) COMPLIED. 5/08/2015 THE BUILDING OFFICIAL ROBERT |
| | BROWN ACCEPTTED THE LETTER FROM ARCHITECT KARIN |
| | MANNCHEN UNDER THE 2010 FL. EXIST. BUILDING CODE 101.5 |
| | EXCEPTION FOR 1 HOUR RATING BETWEEN THE MERCANTILE AND |
| | R3 RESIDENCE ABOVE. |
| | |
| | 3) NOTE FOR CONTRACTOR, CONTRACTORS RESPONSIBILITY: |
| | ASBESTOS SURVEY |
| | RESIDENTIAL LEAD BASED PAINT HAZARD ACT OF 1992 AMENDED |
| | 4/ 21/ 2005 FEDERAL ACT. |
| | |
| | 2010 FBC-EXISTING BUILD. CODE 502.2 NEW AND REPLACEMENT |
| | MATERIALS. EXCEPT AS OTHERWISE REQUIRED OR PERMITTED BY |
| | THIS CODE, MATERIALS PERMITTED BY THE APPLICABLE CODE |
| | FOR NEW CONSTRUCTION SHALL BE USED. LIKE MATERIALS |
| | SHALL BE PERMITTED FOR REPAIRS AND ALTERATIONS, |
| | PROVIDED NO DANGEROUS OR UNSAFE CONDITION, AS DEFINED |
| | IN CHAPTER 2, IS CREATED. HAZARDOUS MATERIALS, SUCH AS |
| | ASBESTOS AND LEAD-BASED PAINT, SHALL NOT BE USED WHERE |
| | THE CODE FOR NEW CONSTRUCTION WOULD NOT PERMIT THEIR |
| | USE IN BUILDINGS OF SIMILAR OCCUPANCY, PURPOSE AND |
| | LOCATION. |
| | |
| | 4A) COMPLIED. |
| | |
| | 4B) COMPLIED. 2304.9.6 LOAD PATH. WHERE WALL FRAMING |
| | MEMBERS ARE NOT CONTINUOUS FROM FOUNDATION SILL TO |
| | ROOF, THE MEMBERS SHALL BE SECURED TO ENSURE A |
| | CONTINUOUS LOAD PATH. WHERE REQUIRED, SHEET METAL |
| | CLAMPS, TIES OR CLIPS SHALL BE FORMED OF GALVANIZED |
| | STEEL OR OTHER APPROVED CORROSION-RESISTANT MATERIAL |
| | NOT LESS THAN 0.040 INCH (1.01 MM) NOMINAL THICKNESS. |
| | THE UPDATED PLANS SHOW STRAPS FROM THE POST TO FLOOR |
| | JOIST BUT NOT TO THE ROOF CEILING JOIST. |
| | |
| | 4C) COMPLIED. |
| | |
| | 4D) COMPLIED. |
| | |
| | 5) COMPLIED. |
| | |
| | 6) 3RD REQUEST. WINDOW NOTE # 1 INDICATES THE |
| | INSTALATION OF NEW WINDOWS WITH A COMPABLE OPTION FOR |
| | OPERABLE SHUTTERS, NO OPTIONS!!!! ITS A EITHER OR NO |
| | OPTIONS. 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE, CHAPTER 1, ADMINISTRATION, 107.2.1 SUCH |
| | DRAWINGS AND SPECIFICATIONS SHALL CONTAIN INFORMATION, |
| | IN THE FORM OF NOTES OR OTHERWISE, AS TO THE QUALITY OF |
| | MATERIALS, WHERE QUALITY IS ESSENTIAL TO CONFORMITY |
| | WITH THE TECHNICAL CODES. SUCH INFORMATION SHALL BE |
| | SPECIFIC, AND THE TECHNICAL CODES SHALL NOT BE CITED AS |
| | A WHOLE OR IN PART, NOR SHALL THE TERM "LEGAL" OR ITS |
| | EQUIVALENT BE USED AS A SUBSTITUTE FOR SPECIFIC |
| | INFORMATION. |
| | |
| | 7) 3RD REQUEST. 2010 FBC-B 1609.1.2 PROTECTION OF |
| | OPENINGS, 1609.6.4.41 COMPONENTS & CLADDING |
| | |
| | FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV. |
| | 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION |
| | SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS: |
| | (31)(A) EXTERIOR DOORS. |
| | (B) WINDOWS & MULLIONS |
| | (E) STORM SHUTTERS |
| | |
| | 8) 3RD REQUEST. 2010 FBC 107.3.4.1 PRODUCT APPROVALS. |
| | THOSE PRODUCTS WHICH ARE REGULATED BY THE DCA RULE |
| | 9N-03 SHALL BE REVIEWED AND APPROVED IN WRITING BY THE |
| | DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR |
| | JURISDICTIONAL APPROVAL. |
| | FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR |
| | SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS, |
| | SHOP DRAWINGS ETC.. |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & |
| | REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |
| | A THOROUGH REVIEW CAN NOT BE MADE AT THIS TIME, AS A |
| | RESULT OF THE ADDITIONAL INFORMATION REQUESTED |
| | ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF |
| | THIS REVIEW. |
| | |