Plan Review Notes
Plan Review Notes For Permit 15010809
Permit Number 15010809
Review Stop M
Sequence Number 2
Notes
Date Text
2015-04-22 10:08:55PLAN DENIED
 1) PROVIDE GRILL SIZE ON PLAN PER 107 2010 FBC.
 2) PROVIDE FRESH AIR CALCULATIONS ON PLAN PER
 TABLE 403.3 FBC (M) 2010
 3) SHOW LOCATION OF CONDENSER ON PLAN. IF
 CONDENSER IS ON THE ROOF REFER TO SECTION
 301.12 WIND RESISTANCE 2010 FBC (M)
  