Date Text
2015-04-09 11:45:5815010809
 1813 TAMARIND AVE.
 RESIDENTIAL RENOVATION
 2ND REVIEW
  
 PLEASE REVISE THE PLANS IN RESPONSE TO THE FOLLOWING
 ELECTRICAL REVIEW COMMENTS. SEVERALOF THE INITIAL
 RESPONSES TO THE ORIGINAL REVIEW REQUIRE CLARIFICATION
 OR ADDITIONAL INFORMATION.
  
 SHOW THE COMPLETE ELECTRICAL SYSTEM INCLUDING ALL
 SERVICES TO THE BUILDING. THE ELECTRIC SERVICE
 DISCONNECT AS DEPICTED MAY NOT BE LOCATED ON THE SECOND
 FLOOR. A BUILDING OR OTHER STRUCTURE SERVED SHALL BE
 SUPPLIED BY ONLY ONE SERVICE. THIS BUILDING REQUIRES
 MAIN SERVICE DISCONNECTS FOR EACH OCCUPANCY WHICH ARE
 TO BE LOCATED OUTSIDE THE BUILDING AND AT THE POINT OF
 SERVICE. MAIN DISCONNECTS ARE REQUIRED TO BE GROUPED IN
 ONE LOCATION. NEC 230.2 NEC 110.20, 230.66, 230.79,
 230.71
  
 A BUILDING WHICH HAS MULTIPLE ELECTRIC SERVICES MUST
 HAVE ALL GROUNDING ELECTRODE CONDUCTORS BONDED
 TOGETHER. NEC 250.58
  
 A BONDING STRIP IS REQUIRED AT THE ELECTRIC SERVICE
 GROUND. NEC 250.94
  
 INDICATE THE FAULT CURRENT CAPACITY REQUIRED FOR THE
 ELECTRIC SERVICE AND ELECTRIC PANELS. NEC 110.9, 110.10
  
 PROVIDE INTERCONNECTED SMOKE ALARMS BOTH WITHIN AND
 OUTSIDE EACH SLEEPING AREA. IF THE BUILDING HAS GAS
 APPLIANCES, AN ATTACHED GARAGE OR A FIREPLACE, A CARBON
 MONOXIDE DETECTOR IS REQUIRED WITHIN TEN FEET OF EACH
 ROOM USED FOR SLEEPING. 2010 FBC R314, 315
  
 ARC FAULT CIRCUIT PROTECTION IS REQUIRED FOR ALL BRANCH
 CIRCUITS SUPPLYING OUTLETS. NEC 210.12
  
 PROVIDE A 20 AMPERE BRANCH CIRCUIT FOR THE BATHROOMS.
 NEC 210.11 (C)(3)
  
 PROVIDE A 20 AMPERE BRANCH CIRCUIT FOR THE DINING AREA
 OUTLETS. NEC 210.52(B)(1)
  
 ROBERT LECKY
 ELECTRICAL PLANS EXAMINER
  