| Date |
Text |
| 2015-04-09 11:45:58 | 15010809 |
| | 1813 TAMARIND AVE. |
| | RESIDENTIAL RENOVATION |
| | 2ND REVIEW |
| | |
| | PLEASE REVISE THE PLANS IN RESPONSE TO THE FOLLOWING |
| | ELECTRICAL REVIEW COMMENTS. SEVERALOF THE INITIAL |
| | RESPONSES TO THE ORIGINAL REVIEW REQUIRE CLARIFICATION |
| | OR ADDITIONAL INFORMATION. |
| | |
| | SHOW THE COMPLETE ELECTRICAL SYSTEM INCLUDING ALL |
| | SERVICES TO THE BUILDING. THE ELECTRIC SERVICE |
| | DISCONNECT AS DEPICTED MAY NOT BE LOCATED ON THE SECOND |
| | FLOOR. A BUILDING OR OTHER STRUCTURE SERVED SHALL BE |
| | SUPPLIED BY ONLY ONE SERVICE. THIS BUILDING REQUIRES |
| | MAIN SERVICE DISCONNECTS FOR EACH OCCUPANCY WHICH ARE |
| | TO BE LOCATED OUTSIDE THE BUILDING AND AT THE POINT OF |
| | SERVICE. MAIN DISCONNECTS ARE REQUIRED TO BE GROUPED IN |
| | ONE LOCATION. NEC 230.2 NEC 110.20, 230.66, 230.79, |
| | 230.71 |
| | |
| | A BUILDING WHICH HAS MULTIPLE ELECTRIC SERVICES MUST |
| | HAVE ALL GROUNDING ELECTRODE CONDUCTORS BONDED |
| | TOGETHER. NEC 250.58 |
| | |
| | A BONDING STRIP IS REQUIRED AT THE ELECTRIC SERVICE |
| | GROUND. NEC 250.94 |
| | |
| | INDICATE THE FAULT CURRENT CAPACITY REQUIRED FOR THE |
| | ELECTRIC SERVICE AND ELECTRIC PANELS. NEC 110.9, 110.10 |
| | |
| | PROVIDE INTERCONNECTED SMOKE ALARMS BOTH WITHIN AND |
| | OUTSIDE EACH SLEEPING AREA. IF THE BUILDING HAS GAS |
| | APPLIANCES, AN ATTACHED GARAGE OR A FIREPLACE, A CARBON |
| | MONOXIDE DETECTOR IS REQUIRED WITHIN TEN FEET OF EACH |
| | ROOM USED FOR SLEEPING. 2010 FBC R314, 315 |
| | |
| | ARC FAULT CIRCUIT PROTECTION IS REQUIRED FOR ALL BRANCH |
| | CIRCUITS SUPPLYING OUTLETS. NEC 210.12 |
| | |
| | PROVIDE A 20 AMPERE BRANCH CIRCUIT FOR THE BATHROOMS. |
| | NEC 210.11 (C)(3) |
| | |
| | PROVIDE A 20 AMPERE BRANCH CIRCUIT FOR THE DINING AREA |
| | OUTLETS. NEC 210.52(B)(1) |
| | |
| | ROBERT LECKY |
| | ELECTRICAL PLANS EXAMINER |
| | |