| 2015-02-10 13:43:39 | 15010809 |
| | 1813 TAMARIND AVE. |
| | RESIDENTIAL RENOVATION |
| | |
| | THE SCOPE OF THE PROPOSED ELECTRICAL WORK IS NOT CLEAR. |
| | THE PROPERTY APPEARS TO HAVE MORE THAN ONE FLOOR WITH A |
| | COMMERCIAL USE. PLEASE REVISE THE PLANS IN RESPONSE TO |
| | THE FOLLOWING ELECTRICAL REVIEW COMMENTS. SHOW THE |
| | COMPLETE ELECTRICAL SYSTEM. |
| | |
| | A BUILDING OR OTHER STRUCTURE SERVED SHALL BE SUPPLIED |
| | BY ONLY ONE SERVICE. THIS BUILDING REQUIRES A MAIN |
| | SERVICE DISCONNECT FOR EACH OCCUPANCY AND LOCATED |
| | OUTSIDE AT THE POINT OF SERVICE. MAIN DISCONNECTS ARE |
| | REQUIRED TO BE GROUPED IN ONE LOCATION. NEC 230.2 NEC |
| | 110.20, 230.66, 230.79, 230.71 |
| | |
| | A BONDING STRIP IS REQUIRED AT THE ELECTRIC SERVICE |
| | GROUND NEC 250.94 |
| | |
| | INDICATE THE FAULT CURRENT CAPACITY REQUIRED FOR THE |
| | ELECTRIC SERVICE AND ELECTRIC PANELS. NEC 110.9, 110.10 |
| | |
| | REMODELING OF AN EXISTING STRUCTURE IS REQUIRED TO |
| | INCLUDE INTERCONNECTED SMOKE ALARMS BOTH WITHIN AND |
| | OUTSIDE EACH SLEEPING AREA. IF THE BUILDING HAS GAS |
| | APPLIANCES, AN ATTACHED GARAGE OR A FIREPLACE, A CARBON |
| | MONOXIDE DETECTOR IS REQUIRED WITHIN TEN FEET OF EACH |
| | ROOM USED FOR SLEEPING. 2010 FBC R314, 315 |
| | |
| | NEW RECEPTACLES MUST BE TAMPER RESISTANT. NEC 406.11 |
| | |
| | GFCI PROTECTED RECEPTACLES ARE REQUIRED AT THE FRONT |
| | ENTRANCE. NEC 210.8, 210.52(E) |
| | |
| | ARC FAULT CIRCUIT PROTECTION IS REQUIRED FOR ALL NEW |
| | GENERAL PURPOSE OUTLETS INCLUDING LIGHTING. NEC 210.12 |
| | |
| | |
| | ROBERT LECKY |
| | ELECTRICAL PLANS EXAMINER |
| | |