2015-02-10 13:43:3915010809
 1813 TAMARIND AVE.
 RESIDENTIAL RENOVATION
  
 THE SCOPE OF THE PROPOSED ELECTRICAL WORK IS NOT CLEAR.
 THE PROPERTY APPEARS TO HAVE MORE THAN ONE FLOOR WITH A
 COMMERCIAL USE. PLEASE REVISE THE PLANS IN RESPONSE TO
 THE FOLLOWING ELECTRICAL REVIEW COMMENTS. SHOW THE
 COMPLETE ELECTRICAL SYSTEM.
  
 A BUILDING OR OTHER STRUCTURE SERVED SHALL BE SUPPLIED
 BY ONLY ONE SERVICE. THIS BUILDING REQUIRES A MAIN
 SERVICE DISCONNECT FOR EACH OCCUPANCY AND LOCATED
 OUTSIDE AT THE POINT OF SERVICE. MAIN DISCONNECTS ARE
 REQUIRED TO BE GROUPED IN ONE LOCATION. NEC 230.2 NEC
 110.20, 230.66, 230.79, 230.71
  
 A BONDING STRIP IS REQUIRED AT THE ELECTRIC SERVICE
 GROUND NEC 250.94
  
 INDICATE THE FAULT CURRENT CAPACITY REQUIRED FOR THE
 ELECTRIC SERVICE AND ELECTRIC PANELS. NEC 110.9, 110.10
  
 REMODELING OF AN EXISTING STRUCTURE IS REQUIRED TO
 INCLUDE INTERCONNECTED SMOKE ALARMS BOTH WITHIN AND
 OUTSIDE EACH SLEEPING AREA. IF THE BUILDING HAS GAS
 APPLIANCES, AN ATTACHED GARAGE OR A FIREPLACE, A CARBON
 MONOXIDE DETECTOR IS REQUIRED WITHIN TEN FEET OF EACH
 ROOM USED FOR SLEEPING. 2010 FBC R314, 315
  
 NEW RECEPTACLES MUST BE TAMPER RESISTANT. NEC 406.11
  
 GFCI PROTECTED RECEPTACLES ARE REQUIRED AT THE FRONT
 ENTRANCE. NEC 210.8, 210.52(E)
  
 ARC FAULT CIRCUIT PROTECTION IS REQUIRED FOR ALL NEW
 GENERAL PURPOSE OUTLETS INCLUDING LIGHTING. NEC 210.12
  
  
 ROBERT LECKY
 ELECTRICAL PLANS EXAMINER
  