| Plan Review Notes For Permit 15010788 |
| Permit Number |
15010788 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2015-02-26 17:59:16 | PLAN DENIED | | | 1) PROVIDE A FUEL PIPING PLAN FROM SECONDARY FUEL TANK | | | TO GENERATOR | | | PER SECTION 107 FBC 2010 | | | 2) PROVIDE THE SIZE OF THE SECONDARY FUEL TANK ON THE | | | PLAN | | | SUBMIT THE PLAN TO PALM BEACH COUNTY DERM BE FOR | | | SUBMITTING IT TO | | | THE CITY FOR REVIEW. | | | 3) PROVIDE A PLAN SHOWING SIZE AND LOCATION OF THE | | | EXHAUST FROM THE | | | GENERATOR AND THE TERMINATION OF THE EXHAUST. | | | 4) REFER TO SECTION 1305.2.1 FLOOD HAZARD FLOOD | | | ELEVATION IS 14.5 FT | | | FLOOD ZONE IS A 8 | | | | | | PLAN REVIEW BY HAROLD MOSER | | | [email protected] | | | OFFICE 561-805-6732 | | | FAX 561-805-6676 | | | |
|