Plan Review Notes
Plan Review Notes For Permit 15010788
Permit Number 15010788
Review Stop E
Sequence Number 1
Notes
Date Text
2015-02-26 16:57:092/26/2015
 PROJECT: GENERATOR
 PERMIT#: 15010788
 CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC
 ,2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1,
 ADMINISTRATION, 2012 FBC SUPPLEMENTS.
 1ST ELECTRICAL PLAN REVIEW
 ACTION: DENIED
  
 1) THE SUBJECT PROPERTY IS LOCATED IN A FLOOD ZONE.
 PROVIDE AN ELEVATION CERTIFICATE OR OTHER APPROVED
 EVIDENCE THAT THE PROJECT SITE MEETS THE REQUIRED ONE
 FT FREEBOARD. FBC 1612.4
  
 2) REVISE RISER DIAGRAM TO INCLUDE CONDUIT AND WIRE
 SIZES FOR FEEDERS.
  
 3) REVISE THE RISER DIAGRAM TO INCLUDE THE CORRECT
 SYSTEM VOLTAGE ON BOTH THE UTILITY AND THE GENERATOR.
 IT APPEARS BY THE EQUIPMENT SUBMITTALS THE SYSTEM
 VOLTAGE IS PROVIDED AT 277/480 HOWEVER THE RISER DIARAM
 ILLUSTRATES A SYSTEM VOLTAGE OF 120/208 AT THE SERVICE
 UTILITY. CLARIFY FOR CONSISTANCY.
  
 4) CHECK THE APPROPRIATE BOXES IN THE EQUIPMENT
 SUBMITTALS TO INDICATE THE ACTUAL MODEL NUMBER, SYSTEM
 VOLTAGE ETC..
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. SEE LINK:
 HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/
 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF
  
 ADDITIONALLY, IT IS REQUIRED TO INSERT THE CORRECTED
 PAGES INTO THE DENIED SUBMITTAL PACKAGE. VOID THE
 PREVIOUSLY REVIEWED SHEETS AND LEAVE FOR COMPARATIVE
 REVIEW.
  
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]
  