| Plan Review Notes For Permit 15010788 |
| Permit Number |
15010788 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2015-03-20 10:11:07 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6724 | | | | | | 1. PROVIDE AN ENGINEERED STRUCTURAL DETAIL FOR PROPOSED | | | INSTALLATION. FBC 1604.9, FBC1609. THIS IS TO INCLUDE | | | WIND DESIGN CRITERIA INCLUDING RISK FACTOR. | | | | | | 2. FBC 1603.1.7, INCLUDE THE INFORMATION REQUIRED FOR | | | FLOOD DESIGN DATA. SEE ASCE 24 REGARDING FREEBOARD | | | REQUIREMENTS. | | | |
|