2015-01-30 14:05:58BUILDING PLAN REVIEW
 PERMIT: 15010772
 ADD: 5300 EAST AV. / ATRIUM
 CONT: TRILLIUM
 TEL: ( 561)371-6825
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: FRIDAY/ JAN. 30/2015
 ACTION: DENIED
  
 1) SHEET A1 THE ATRIUM HEAD GLAZING DETAIL DOES NOT
 SHOW FIRE SPRINKLERS IN ACCORDANCE WITH THE 2010 FBC-B
 404.6 ENCLOSURE OF ATRIUMS.
 ATRIUM SPACES SHALL BE SEPARATED FROM ADJACENT SPACES
 BY A 1-HOUR FIRE BARRIER CONSTRUCTED IN ACCORDANCE WITH
 SECTION 707 OR A HORIZONTAL ASSEMBLY CONSTRUCTED IN
 ACCORDANCE WITH SECTION 712, OR BOTH.
 EXCEPTIONS:
 1. A GLASS WALL FORMING A SMOKE PARTITION WHERE
 AUTOMATIC SPRINKLERS ARE SPACED 6 FEET (1829 MM) OR
 LESS ALONG BOTH SIDES OF THE SEPARATION WALL, OR ON THE
 ROOM SIDE ONLY IF THERE IS NOT A WALKWAY ON THE ATRIUM
 SIDE, AND BETWEEN 4 INCHES AND 12 INCHES (102 MM AND
 305 MM) AWAY FROM THE GLASS AND DESIGNED SO THAT THE
 ENTIRE SURFACE OF THE GLASS IS WET UPON ACTIVATION OF
 THE SPRINKLER SYSTEM WITHOUT OBSTRUCTION. THE GLASS
 SHALL BE INSTALLED IN A GASKETED FRAME SO THAT THE
 FRAMING SYSTEM DEFLECTS WITHOUT BREAKING (LOADING) THE
 GLASS BEFORE THE SPRINKLER SYSTEM OPERATES.
  
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  