| 2015-01-26 18:01:02 | PLAN REVIEW COMMENTS |
| | |
| | 1ST REVIEW: FBC 2010 , NEC 2008 |
| | ROBERT MCDOUGAL, CBO |
| | COMMERCIAL COMBINATION PLANS EXAMINER |
| | (561) 805-6714 |
| | [email protected] |
| | |
| | DENIED BY ELECTRICAL |
| | PLEASE ADDRESS THE ITEMS NOTED BELOW: |
| | |
| | 1) FBC 107.2.1 - INFORMATION ON CONSTRUCTION DOCUMENTS. |
| | ALL INFORMATION, DRAWINGS, SPECIFICATIONS AND |
| | ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE OF |
| | THE PERSON RESPONSIBLE FOR THE DESIGN. |
| | |
| | 2) FBC-R314.3.1 WHEN ALTERATIONS, REPAIRS OR ADDITIONS |
| | REQUIRING A PERMIT OCCUR, OR WHEN ONE OR MORE SLEEPING |
| | ROOMS ARE ADDED OR CREATED IN EXISTING DWELLINGS, THE |
| | INDIVIDUAL DWELLING UNIT SHALL BE EQUIPPED WITH SMOKE |
| | ALARMS LOCATED AS REQUIRED FOR NEW DWELLINGS. |
| | |
| | 3) NEC 220.40 - SUBMIT ELECTRICAL LOAD CALCULATIONS. |
| | |
| | 4) FBC 107.3.5.3 - SUBMIT A PANEL SCHEDULE. |
| | |
| | 5) NEC 210.11 (C) (3) AT LEAST ONE 20 - AMP BRANCH |
| | CIRCUIT SHALL BE PROVIDED TO SUPPLY BATHROOM RECEPTACLE |
| | OUTLETS. |
| | |
| | 6) NEC 210.12 (B) - OUTLETS ARE REQUIRED TO BE AFCI |
| | PROTECTED. |
| | |
| | 7) NEC 406.11 - TAMPER-RESISTANT RECEPTACLES ARE |
| | REQUIRED. |
| | |
| | 8) NEC 210.52 (B) (3) - KITCHEN COUNTER TOP RECEPTACLES |
| | SHALL BE SUPPLIED BY NO FEWER THAN TWO SMALL APPLIANCE |
| | BRANCH CIRCUITS. |
| | |
| | 9) NEC 110.26 SUFFICIENT ACCESS AND WORKING SPACE SHALL |
| | BE PROVIDED AND MAINTAINED ABOUT ALL ELECTRICAL |
| | EQUIPMENT TO PERMIT READY AND SAFE OPERATION AND |
| | MAINTENANCE OF SUCH EQUIPMENT. THE WATER HEATER SHALL |
| | NOT ENCROACH INTO THE REQUIRED WORKING SPACE IN FRONT |
| | OF THE ELECTRICAL PANEL. |
| | |
| | 10) IN ORDER TO REDUCE PLAN REVIEW TIMES AND PROVIDE |
| | CLARIFICATION, PLEASE SUBMIT A RESPONSE LETTER |
| | INDICATING HOW EACH OF THE REVIEW COMMENTS HAS BEEN |
| | ADDRESSED. |
| | |
| | |