2015-01-26 18:01:02PLAN REVIEW COMMENTS
  
 1ST REVIEW: FBC 2010 , NEC 2008
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY ELECTRICAL
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) FBC 107.2.1 - INFORMATION ON CONSTRUCTION DOCUMENTS.
 ALL INFORMATION, DRAWINGS, SPECIFICATIONS AND
 ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE OF
 THE PERSON RESPONSIBLE FOR THE DESIGN.
  
 2) FBC-R314.3.1 WHEN ALTERATIONS, REPAIRS OR ADDITIONS
 REQUIRING A PERMIT OCCUR, OR WHEN ONE OR MORE SLEEPING
 ROOMS ARE ADDED OR CREATED IN EXISTING DWELLINGS, THE
 INDIVIDUAL DWELLING UNIT SHALL BE EQUIPPED WITH SMOKE
 ALARMS LOCATED AS REQUIRED FOR NEW DWELLINGS.
  
 3) NEC 220.40 - SUBMIT ELECTRICAL LOAD CALCULATIONS.
  
 4) FBC 107.3.5.3 - SUBMIT A PANEL SCHEDULE.
  
 5) NEC 210.11 (C) (3) AT LEAST ONE 20 - AMP BRANCH
 CIRCUIT SHALL BE PROVIDED TO SUPPLY BATHROOM RECEPTACLE
 OUTLETS.
  
 6) NEC 210.12 (B) - OUTLETS ARE REQUIRED TO BE AFCI
 PROTECTED.
  
 7) NEC 406.11 - TAMPER-RESISTANT RECEPTACLES ARE
 REQUIRED.
  
 8) NEC 210.52 (B) (3) - KITCHEN COUNTER TOP RECEPTACLES
 SHALL BE SUPPLIED BY NO FEWER THAN TWO SMALL APPLIANCE
 BRANCH CIRCUITS.
  
 9) NEC 110.26 SUFFICIENT ACCESS AND WORKING SPACE SHALL
 BE PROVIDED AND MAINTAINED ABOUT ALL ELECTRICAL
 EQUIPMENT TO PERMIT READY AND SAFE OPERATION AND
 MAINTENANCE OF SUCH EQUIPMENT. THE WATER HEATER SHALL
 NOT ENCROACH INTO THE REQUIRED WORKING SPACE IN FRONT
 OF THE ELECTRICAL PANEL.
  
 10) IN ORDER TO REDUCE PLAN REVIEW TIMES AND PROVIDE
 CLARIFICATION, PLEASE SUBMIT A RESPONSE LETTER
 INDICATING HOW EACH OF THE REVIEW COMMENTS HAS BEEN
 ADDRESSED.
  
  