2015-01-26 17:56:58PLAN REVIEW COMMENTS
  
 1ST REVIEW: FBC 2010
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) FBC 107.2.1 - INFORMATION ON CONSTRUCTION DOCUMENTS.
 ALL INFORMATION, DRAWINGS, SPECIFICATIONS AND
 ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE OF
 THE PERSON RESPONSIBLE FOR THE DESIGN.
  
 2) FBC-R314.3.1 WHEN ALTERATIONS, REPAIRS OR ADDITIONS
 REQUIRING A PERMIT OCCUR, OR WHEN ONE OR MORE SLEEPING
 ROOMS ARE ADDED OR CREATED IN EXISTING DWELLINGS, THE
 INDIVIDUAL DWELLING UNIT SHALL BE EQUIPPED WITH SMOKE
 ALARMS LOCATED AS REQUIRED FOR NEW DWELLINGS.
  
 3) PROVIDE A STRUCTURAL DETAIL SHOWING HOW THE EXISTING
 WINDOW OPENINGS WILL BE ENCLOSED. FBC 107.2.1
  
 4) SPECIFY THE WIND SPEED AND EXPOSURE CATEGORY ON THE
 PLANS. FBC 107.2.1.3
  
 5) FBC 107.3.5.3 (5) - PROVIDE WIND DESIGN LOADS/DESIGN
 PRESSURES PURSUANT TO FBC-R301.2.1
  
 6) R310.1 EVERY SLEEPING ROOM SHALL HAVE AT LEAST ONE
 OPERABLE EMERGENCY ESCAPE AND RESCUE OPENING. WHERE
 EMERGENCY ESCAPE AND RESCUE OPENINGS ARE PROVIDED THEY
 SHALL HAVE A SILL HEIGHT OF NOT MORE THAN 44 INCHES
 (1118 MM) ABOVE THE FLOOR.
 R310.1.1 MINIMUM OPENING AREA.
 ALL EMERGENCY ESCAPE AND RESCUE OPENINGS SHALL HAVE A
 MINIMUM NET CLEAR OPENING OF 5.7 SQUARE FEET (0.530
 M2).
 EXCEPTION: GRADE FLOOR OPENINGS SHALL HAVE A MINIMUM
 NET CLEAR OPENING OF 5 SQUARE FEET (0.465 M2).
 R310.1.2 MINIMUM OPENING HEIGHT.
 THE MINIMUM NET CLEAR OPENING HEIGHT SHALL BE 24 INCHES
 (610 MM).
 R310.1.3 MINIMUM OPENING WIDTH.
 THE MINIMUM NET CLEAR OPENING WIDTH SHALL BE 20 INCHES
 (508 MM).
  
 7) THE PRODUCT APPROVALS THAT WERE SUBMITTED FOR THE
 PGT SINGLE HUNG WINDOWS ( NOA NO.11-1013.14 ) HAVE
 INCOMPLETE INSTALLATION INSTRUCTIONS. IT APPEARS THAT
 THE INSTALLATION DRAWINGS WERE NOT SHRUNK DOWN TO FIT
 ON THE 8.5" X 11" PAPER. SUBMIT COMPLETE INSTALLATION
 DRAWINGS AS REQUIRED BY DCA RULE 9N-3.
  
 NOTE: IN ORDER TO REDUCE PLAN REVIEW TIMES AND PROVIDE
 CLARIFICATION, PLEASE SUBMIT A RESPONSE LETTER
 INDICATING HOW EACH OF THE REVIEW COMMENTS HAS BEEN
 ADDRESSED.
  
  
  
  
  
  