 PROJECT: ADX
 PERMIT#: 14050183 REVISION #15010699
 CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC
 ,2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1,
 ADMINISTRATION, 2012 FBC SUPPLEMENTS.
 1ST ELECTRICAL PLAN REVIEW
 ACTION:
  
 1) PROVIDE FOR AND INDICATE ON THE PLANS ADAQUATE
 CLEARANCE FOR THE PANELS, FUSABLE DISCONNECTS AND
 ELECTRICAL SERVICE AS REQUIRED BY NEC 110.26.
  
 2) ELECTRICAL SPECIFICATIONS
 #1) CALLS FOR ALL WORK TO BE DONE IN ACCORDANCE WITH
 THE 2011 NEC. CORRECT THIS TO READ THE 2008 NEC.
 #11) CALLS FOR ALL EXTERIOR LIGHTING TO BE ON SEPARATE
 HOUSE PANEL BY OTHERS. ONLY ONE SERVICE PER BUILDING
 NEC 230.2
  
 3) REVISE CONFLICT AT DRINKING FOUNTAIN. THE NOTE AT
 THE DRINKING FOUNTAIN CALLS FOR BUBBLER ONLY . NO
 ELECTRIC. HOWVER THERE IS AN OUTLET DRAWN IN UNDER THE
 DRINKING FOUNTAIN AND A CIRCUIT IN THE PANEL SCHEDULE
 THAT IS INDICATED AS FEEDING THE DRINKING FOUNTAIN. NEC
 422.52
  
 4) PROVIDE PANEL DESIGNATIONS WITH THE CIRCUIT NUMBERS
 ON THE FLOOR PLAN. WPB AMENDMENTS TO THE FBC 107.2
  
 5) CORRECT CONFLICT IN PANEL SCHEDULES FOR SHOW WINDOW
 LIGHTING CIRCUITS. THE FLOOR PLAN INDICATES THE SHOW
 WINDOW LIGHTING TO BE FIXED LIGHT FIXTURES BEING FED
 FROM PHOTO SENSOR ON UNIT NUMBER 1 PANEL SCHEDULE.
 HOWEVER BOTH PANEL SCHEDULES ALSO INDICATE SHOW WINDOW
 LIGHTING CIRCUITS ON WHAT APPEARS TO BE A SINGLE POLE
 SPACE BUT IS INDICATED AS A 2POLE 30AMP CIRCUIT ON
 #6WIRE. CLEAR UP ALL CONFLICTING INFORMATION.
  
 6) VERIFY SAFETY LABELING FOR ARC FLASH PROTECTION FOR
 THE PANEL BOARDS AND MAIN DISCONNECTING MEANS. NEC
 110.16.
  
 7) VERIFY THE ELECTRICAL SERVICE DISCONNECTING MEANS
 HAS A FAULT CURRENT RATING THAT IS SUFFICIENT AT
 NOMINAL CIRCUIT VOLTAGE FOR THE CURRENT THAT MUST BE
 INTERRUPTED. NEC 110.9
  
 8) THE BRANCH CIRCUIT FEEDING THE UNIT EQUIPMENT SHALL
 BE THE SAME BRANCH CIRCUIT AS THAT SERVING THE NORMAL
 LIGHTING IN THE AREA AND CONNECTED AHEAD OF ANY LOCAL
 SWITCHES. THE BRANCH CIRCUIT THAT FEEDS UNIT EQUIPMENT
 SHALL BE CLEARLY IDENTIFIED AT THE DISTRIBUTION PANEL.
 EMERGENCY LIGHTS APPEAR TO BE INDICATEDON RECEPTACLE
 CIRCUITS. IDENTIFY EACH BRANCH CIRCUIT ON THE FLOOR
 PLAN AND CORRESPOND WITH EACH UNIT PANEL. NEC 700.12
  
 9) PROVIDE A SIGN CIRCUIT AND OUTLET BOX FOR SIGNAGE.
 EACH COMMERCIAL OCCUPANCY ACCESSIBLE TO PEDESTRIANS
 SHALL BE PROVIDED WITH AT LEAST ONE OUTLET SUPPLIED BY
 A BRANCH CIRCUIT RATED AT LEAST 20 AMPERES THAT
 SUPPLIES NO OTHER LOAD. NEC 600.5. THE SIGN CIRCUIT IS
 NOT INCLUDED IN THE LOAD CALCULATION.
  
 10) IDENTIFY THE CIRCUIT AND THE LOAD FOR THE CEILING
 FANS. I DENTIFY THE CIRCUIT IN THE PANEL SCHEDULES AND
 CORRESPONDING ON THE FLOOR PLAN.
  
 11) CONTINUOUS DUTY LOADS HAVE NOT BEEN ACCOUNTED FOR
 IN THE LOAD CALCULATION. NEC 230.(A)(1)
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. SEE LINK:
 HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/
 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF
  
 ADDITIONALLY, IT IS REQUIRED TO INSERT THE CORRECTED
 PAGES INTO THE DENIED SUBMITTAL PACKAGE. VOID THE
 PREVIOUSLY REVIEWED SHEETS AND LEAVE FOR COMPARATIVE
 REVIEW.
  
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]
  