| 2015-02-09 14:13:02 | 2/9/2015 |
| | PROJECT: ADX |
| | PERMIT#: 14050183 REVISION #15010699 |
| | CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC |
| | ,2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1, |
| | ADMINISTRATION, 2012 FBC SUPPLEMENTS. |
| | 1ST ELECTRICAL PLAN REVIEW |
| | ACTION: |
| | |
| | 1) PROVIDE FOR AND INDICATE ON THE PLANS ADAQUATE |
| | CLEARANCE FOR THE PANELS, FUSABLE DISCONNECTS AND |
| | ELECTRICAL SERVICE AS REQUIRED BY NEC 110.26. |
| | |
| | 2) ELECTRICAL SPECIFICATIONS |
| | #1) CALLS FOR ALL WORK TO BE DONE IN ACCORDANCE WITH |
| | THE 2011 NEC. CORRECT THIS TO READ THE 2008 NEC. |
| | #11) CALLS FOR ALL EXTERIOR LIGHTING TO BE ON SEPARATE |
| | HOUSE PANEL BY OTHERS. ONLY ONE SERVICE PER BUILDING |
| | NEC 230.2 |
| | |
| | 3) REVISE CONFLICT AT DRINKING FOUNTAIN. THE NOTE AT |
| | THE DRINKING FOUNTAIN CALLS FOR BUBBLER ONLY . NO |
| | ELECTRIC. HOWVER THERE IS AN OUTLET DRAWN IN UNDER THE |
| | DRINKING FOUNTAIN AND A CIRCUIT IN THE PANEL SCHEDULE |
| | THAT IS INDICATED AS FEEDING THE DRINKING FOUNTAIN. NEC |
| | 422.52 |
| | |
| | 4) PROVIDE PANEL DESIGNATIONS WITH THE CIRCUIT NUMBERS |
| | ON THE FLOOR PLAN. WPB AMENDMENTS TO THE FBC 107.2 |
| | |
| | 5) CORRECT CONFLICT IN PANEL SCHEDULES FOR SHOW WINDOW |
| | LIGHTING CIRCUITS. THE FLOOR PLAN INDICATES THE SHOW |
| | WINDOW LIGHTING TO BE FIXED LIGHT FIXTURES BEING FED |
| | FROM PHOTO SENSOR ON UNIT NUMBER 1 PANEL SCHEDULE. |
| | HOWEVER BOTH PANEL SCHEDULES ALSO INDICATE SHOW WINDOW |
| | LIGHTING CIRCUITS ON WHAT APPEARS TO BE A SINGLE POLE |
| | SPACE BUT IS INDICATED AS A 2POLE 30AMP CIRCUIT ON |
| | #6WIRE. CLEAR UP ALL CONFLICTING INFORMATION. |
| | |
| | 6) VERIFY SAFETY LABELING FOR ARC FLASH PROTECTION FOR |
| | THE PANEL BOARDS AND MAIN DISCONNECTING MEANS. NEC |
| | 110.16. |
| | |
| | 7) VERIFY THE ELECTRICAL SERVICE DISCONNECTING MEANS |
| | HAS A FAULT CURRENT RATING THAT IS SUFFICIENT AT |
| | NOMINAL CIRCUIT VOLTAGE FOR THE CURRENT THAT MUST BE |
| | INTERRUPTED. NEC 110.9 |
| | |
| | 8) THE BRANCH CIRCUIT FEEDING THE UNIT EQUIPMENT SHALL |
| | BE THE SAME BRANCH CIRCUIT AS THAT SERVING THE NORMAL |
| | LIGHTING IN THE AREA AND CONNECTED AHEAD OF ANY LOCAL |
| | SWITCHES. THE BRANCH CIRCUIT THAT FEEDS UNIT EQUIPMENT |
| | SHALL BE CLEARLY IDENTIFIED AT THE DISTRIBUTION PANEL. |
| | EMERGENCY LIGHTS APPEAR TO BE INDICATEDON RECEPTACLE |
| | CIRCUITS. IDENTIFY EACH BRANCH CIRCUIT ON THE FLOOR |
| | PLAN AND CORRESPOND WITH EACH UNIT PANEL. NEC 700.12 |
| | |
| | 9) PROVIDE A SIGN CIRCUIT AND OUTLET BOX FOR SIGNAGE. |
| | EACH COMMERCIAL OCCUPANCY ACCESSIBLE TO PEDESTRIANS |
| | SHALL BE PROVIDED WITH AT LEAST ONE OUTLET SUPPLIED BY |
| | A BRANCH CIRCUIT RATED AT LEAST 20 AMPERES THAT |
| | SUPPLIES NO OTHER LOAD. NEC 600.5. THE SIGN CIRCUIT IS |
| | NOT INCLUDED IN THE LOAD CALCULATION. |
| | |
| | 10) IDENTIFY THE CIRCUIT AND THE LOAD FOR THE CEILING |
| | FANS. I DENTIFY THE CIRCUIT IN THE PANEL SCHEDULES AND |
| | CORRESPONDING ON THE FLOOR PLAN. |
| | |
| | 11) CONTINUOUS DUTY LOADS HAVE NOT BEEN ACCOUNTED FOR |
| | IN THE LOAD CALCULATION. NEC 230.(A)(1) |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. SEE LINK: |
| | HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/ |
| | 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF |
| | |
| | ADDITIONALLY, IT IS REQUIRED TO INSERT THE CORRECTED |
| | PAGES INTO THE DENIED SUBMITTAL PACKAGE. VOID THE |
| | PREVIOUSLY REVIEWED SHEETS AND LEAVE FOR COMPARATIVE |
| | REVIEW. |
| | |
| | DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421, |
| | 561-805-6717 OR [email protected] |
| | |