| | PROJECT: CONDO RENOVATION 1101 |
| | PERMIT#: 15010696 |
| | CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC |
| | ,2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1, |
| | ADMINISTRATION, 2012 FBC SUPPLEMENTS. |
| | 1ST ELECTRICAL PLAN REVIEW |
| | ACTION: APPROVED WITH EXCEPTION. |
| | |
| | PROVIDE AS BUILT PLANS TO THE INSPECTOR ADDRESSING THE |
| | FOLLOWING COMMENTS: |
| | |
| | 1) PROVIDE A PANEL SCHEDULE. EVERY CIRCUIT AND CIRCUIT |
| | MODIFICATION SHALL BE LEGIBLY IDENTIFIED AS TO ITS |
| | CLEAR, EVIDENT, AND SPECIFIC PURPOSE OR USE. NEC 408.4 |
| | |
| | 2) PROVIDE CIRCUIT NUMBERS ON THE FLOOR PLAN |
| | CORRESPONDING TO THE PANEL SCHEDULE PROVIDED. |
| | CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT CLARITY |
| | TO INDICATE THE LOCATION, NATURE AND EXTENT OF THE WORK |
| | PROPOSED AND SHOW IN DETAIL THAT IT WILL CONFORM TO THE |
| | PROVISIONS OF THIS CODE AND RELEVANT LAWS, ORDINANCES, |
| | RULES AND REGULATIONS, AS DETERMINED BY THE BUILDING |
| | OFFICIAL. WPB AMENDMENTS TO THE FBC 107.3.2 |
| | |
| | 3) VERIFY SMOKE DETECTORS ARE EXISTING OR INSTALL AS |
| | REQUIRED. WHEN ALTERATIONS, REPAIRS, OR ADDITIONS |
| | REQUIRING A PERMIT OCCUR, OR WHEN ONE OR MORE SLEEPING |
| | ROOMS ARE ADDED OR CREATED IN EXISTING DWELLINGS, THE |
| | INDIVIDUAL DWELLING UNIT SHALL BE EQUIPPED WITH SMOKE |
| | ALARMS LOCATED AS REQUIRED FOR NEW DWELLINGS. |
| | FBC-RESIDENTIAL 314 AND 315. |
| | |
| | 4) METAL FRAMING MEMBERS SHALL BE BONDED TO THE |
| | EQUIPMENT GROUNDING CONDUCTOR FOR THE CIRCUIT THAT MAY |
| | ENERGIZE THE FRAMING AND BE SIZED IN ACCORDANCE WITH |
| | THE NEC TABLE 250.122. FOR THE PURPOSE OF THIS SECTION, |
| | A GROUNDED METAL OUTLET BOX ATTACHED TO THE FRAMING |
| | SHALL BE PERMITTED. FBC 2704 BONDING METAL FRAMING |
| | MEMBERS |
| | |
| | 5) VERIFY BATHROOM CIRCUIT REQUIRED. IN ADDITION TO THE |
| | NUMBER OF BRANCH CIRCUITS REQUIRED BY OTHER PARTS OF |
| | THIS SECTION, AT LEAST ONE 20-AMPERE BRANCH CIRCUIT |
| | SHALL BE PROVIDED TO SUPPLY BATHROOM RECEPTACLE |
| | OUTLET(S). SUCH CIRCUITS SHALL HAVE NO OTHER OUTLETS. |
| | NEC 210.11(C)(3) |
| | |
| | 6) AT LEAST ONE RECEPTACLE OUTLET SHALL BE INSTALLED IN |
| | BATHROOMS WITHIN (3 FT) OF THE OUTSIDE EDGE OF EACH |
| | BASIN. THE RECEPTACLE OUTLET SHALL BE LOCATED ON A WALL |
| | OR PARTITION THAT IS ADJACENT TO THE BASIN OR BASIN |
| | COUNTERTOP, OR INSTALLED ON THE SIDE OR FACE OF THE |
| | BASIN CABINET NOT MORE THAN (12 IN.) BELOW THE |
| | COUNTERTOP. NEC 210.52 (D) |
| | |
| | DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421, |
| | 561-805-6717 OR [email protected] |
| | |
| | |
| | |