2015-01-30 10:37:211/30/2015
 PROJECT: CONDO RENOVATION 1101
 PERMIT#: 15010696
 CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC
 ,2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1,
 ADMINISTRATION, 2012 FBC SUPPLEMENTS.
 1ST ELECTRICAL PLAN REVIEW
 ACTION: APPROVED WITH EXCEPTION.
  
 PROVIDE AS BUILT PLANS TO THE INSPECTOR ADDRESSING THE
 FOLLOWING COMMENTS:
  
 1) PROVIDE A PANEL SCHEDULE. EVERY CIRCUIT AND CIRCUIT
 MODIFICATION SHALL BE LEGIBLY IDENTIFIED AS TO ITS
 CLEAR, EVIDENT, AND SPECIFIC PURPOSE OR USE. NEC 408.4
  
 2) PROVIDE CIRCUIT NUMBERS ON THE FLOOR PLAN
 CORRESPONDING TO THE PANEL SCHEDULE PROVIDED.
 CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT CLARITY
 TO INDICATE THE LOCATION, NATURE AND EXTENT OF THE WORK
 PROPOSED AND SHOW IN DETAIL THAT IT WILL CONFORM TO THE
 PROVISIONS OF THIS CODE AND RELEVANT LAWS, ORDINANCES,
 RULES AND REGULATIONS, AS DETERMINED BY THE BUILDING
 OFFICIAL. WPB AMENDMENTS TO THE FBC 107.3.2
  
 3) VERIFY SMOKE DETECTORS ARE EXISTING OR INSTALL AS
 REQUIRED. WHEN ALTERATIONS, REPAIRS, OR ADDITIONS
 REQUIRING A PERMIT OCCUR, OR WHEN ONE OR MORE SLEEPING
 ROOMS ARE ADDED OR CREATED IN EXISTING DWELLINGS, THE
 INDIVIDUAL DWELLING UNIT SHALL BE EQUIPPED WITH SMOKE
 ALARMS LOCATED AS REQUIRED FOR NEW DWELLINGS.
 FBC-RESIDENTIAL 314 AND 315.
  
 4) METAL FRAMING MEMBERS SHALL BE BONDED TO THE
 EQUIPMENT GROUNDING CONDUCTOR FOR THE CIRCUIT THAT MAY
 ENERGIZE THE FRAMING AND BE SIZED IN ACCORDANCE WITH
 THE NEC TABLE 250.122. FOR THE PURPOSE OF THIS SECTION,
 A GROUNDED METAL OUTLET BOX ATTACHED TO THE FRAMING
 SHALL BE PERMITTED. FBC 2704 BONDING METAL FRAMING
 MEMBERS
  
 5) VERIFY BATHROOM CIRCUIT REQUIRED. IN ADDITION TO THE
 NUMBER OF BRANCH CIRCUITS REQUIRED BY OTHER PARTS OF
 THIS SECTION, AT LEAST ONE 20-AMPERE BRANCH CIRCUIT
 SHALL BE PROVIDED TO SUPPLY BATHROOM RECEPTACLE
 OUTLET(S). SUCH CIRCUITS SHALL HAVE NO OTHER OUTLETS.
 NEC 210.11(C)(3)
  
 6) AT LEAST ONE RECEPTACLE OUTLET SHALL BE INSTALLED IN
 BATHROOMS WITHIN (3 FT) OF THE OUTSIDE EDGE OF EACH
 BASIN. THE RECEPTACLE OUTLET SHALL BE LOCATED ON A WALL
 OR PARTITION THAT IS ADJACENT TO THE BASIN OR BASIN
 COUNTERTOP, OR INSTALLED ON THE SIDE OR FACE OF THE
 BASIN CABINET NOT MORE THAN (12 IN.) BELOW THE
 COUNTERTOP. NEC 210.52 (D)
  
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]
  
  
  