| Plan Review Notes For Permit 15010691 |
| Permit Number |
15010691 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2015-02-05 06:46:09 | 1. FBC 107.2.1. DRAWINGS TO BEAR SIGNATURE FOR PERSON | | | RESPONSIBLE FOR DESIGN. | | | 2. FBC 107.3.5.3. CIRCUITS TO BE SHOWN ON FLOOR PLAN | | | FOR ADDITION OF EMERGENCY LIGHTS AND EXIT SIGNS. | | | 3. N.E.C. 700.12(F).THE BRANCH CIRCUIT FEEDING THE | | | EMERGENCY LIGHTS(UNIT EQUIPMENT) SHALL BE THE SAME | | | BRANCH CIRCUIT AS THAT SERVING THE NORMAL LIGHTING IN | | | THE AREA . |
|