| Plan Review Notes For Permit 15010690 |
| Permit Number |
15010690 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2015-01-23 09:13:15 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6724 | | | | | | 1. ENGINEERING REQUIRED, FS 471. | | | | | | 2. REVISE APPLICATION DESCRIPTION TO INDICATE LOCATION | | | OF PROPOSED IMPROVEMENT, FBC 107. OR, PROVIDE A PLAN. | | | THIS INFORMATION SHOULD BE EASILY DISCERNED, NOT IN THE | | | MIDDLE OF A SPECIFICATION. | | | | | | 3. PROVIDE A COPY OF THE CONTRACT FOR THIS JOB, FBC | | | 109. | | | | | | 4. NO INFORMATION REGARDING CHANGE IN ELEVATION | | | DIFFERENCES, AND HOW THIS IMPROVEMENT WILL AFFECT MEANS | | | OF EGRESS AND ACCESSIBILITY AND/OR FAIR HOUSING AS | | | APPLICABLE, FBC 2010 BUILDING CHAPTER 10, FBC 2010 | | | ACCESSIBILITY. | | | | | | PROVIDE AN ARCHITECTURAL PLAN WHICH SHOWS ELEVATION | | | DIFFERENCES, ALL DOORS WHICH ACCESS THIS BALCONY. | | | INCLUDE THE OCCUPANCY CLASSIFICATION. CONFIRM (ON THE | | | PLAN, NOT IN A LETTER) THAT THIS BALCONY SERVES ONLY | | | ONE RESIDENTIAL UNIT, IF THIS IS THE CASE. | | | | | | 5. SCOPE NOT CLEAR, FBC 107. APPLICATION INCLUDES | | | REMOVAL OF TILE AND WATERPROOFING, BUT DOES NOT INCLUDE | | | INSTALLATION OF A FLOOR FINISH. PLEASE CLARIFY. | | | | | | 6. PROVIDE A PLAN WHICH SHOWS WHAT IS UNDERNEATH THIS | | | BALCONY, FBC 1207.2, FBC 1207.3. | | | | | | | | | NOT ENOUGH INFORMATION SUBMITTED TO PROVIDE A COMPLETE | | | CHECKLIST. |
|