Plan Review Notes
Plan Review Notes For Permit 15010671
Permit Number 15010671
Review Stop E
Sequence Number 1
Notes
Date Text
2015-02-06 13:52:27PLAN REVIEW COMMENTS
  
 1ST REVIEW: FBC 2010
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY ELECTRICAL
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) NEC 240.24(A) & (B) PANELS SHALL BE READILY
 ACCESSIBLE AND EACH OCCUPANT SHALL HAVE READY ACCESS.
 SPECIFY THE LOCATION OF THE PANEL FOR UNIT #2 ON THE
 ELECTRICAL FLOOR PLAN (SHEET R E-1).
  
 2) A 200 AMP ELECTRIC PANEL IS SHOWN ON SHEET R-1 FOR
 UNIT #2 ON THE BUILDING FLOOR PLAN. THE ELECTRICAL
 RISER PLAN ON SHEET R E-1 SHOWS BOTH PANELS AS 150 AMP.
 PLEASE CORRECT. FBC 107.2.1
  
 3) A SMOKE ALARM IS REQUIRED IN THE BEDROOM OF UNIT #2.
 TWO SMOKE ALARMS ARE SHOWN IN THE LIVING ROOM. FBC
 FBC-R314.3.1
  
 4) NEC 210.52(A) - (H) OUTLET SPACING, IT APPEARS SOME
 POINTS ALONG THE WALL EXCEED 6' FROM AN OUTLET.
  
 5) NEC 210.52 (C) (1) - A RECEPTACLE OUTLET SHALL BE
 INSTALLED AT EACH COUNTERTOP SPACE 12 INCHES OR WIDER
 SO THAT NO POINT ALONG THE WALL LINE IS MORE THAN 2
 FEET MEASURED HORIZONTALLY FROM A RECEPTACLE OUTLET IN
 THAT SPACE.
  
 6) NEC 210.52 (E)(1) - AT LEAST ONE RECEPTACLE OUTLET
 ACCESSIBLE WHILE STANDING AT GRADE LEVEL AND LOCATED
 NOT MORE THAN 6.5 FT. ABOVE GRADE SHALL BE INSTALLED AT
 THE FRONT AND BACK OF EACH UNIT OF THE DWELLING.
  
  
  