| 2015-05-23 06:03:49 | 1) SHT. F-PP110C - THE STORM DRAIN AT GRIDLINE F7 IS |
| | SHOWN AS 10" (8300 SQ.FT.) AND AS AN 8" STORM DRAIN ON |
| | SHT.F-PP402. CLARIFY. |
| | 2) SHT. F-PP402 SHOWS 2" DRAINS FROM THE AUTOMATIC FIRE |
| | SPRINKLER SYSTEM DISCHARGING INTO THE STORM DRAINAGE |
| | SYSTEM. THIS ARRANGEMENT APPEARS IN SEVERAL LOCATIONS |
| | AND ON SEVERAL PAGES.THE SPRINKLER SYSTEM CANNOT |
| | DISCHARGE TO THE STORM DRAINAGE SYSTEM PER CITY OF WPB |
| | CODE OF ORDINANCES ARTICLE V, SEC.90-203. |
| | 3) SHT.F-PP402 - THERE IS A HORIZONTAL 4" ST NEAR |
| | GRIDLINE D-12 THAT JUST ENDS AND CONNECTS TO NOTHING. |
| | MAY BE TYPO. CLARIFY. |
| | 4) SHT. F-PP402 - 4" ST UP TO GROUND LEVEL NOT SHOWN ON |
| | PLAN F-PP110A BETWEEN COLS."C" & "D" AND "12" & "13". |
| | CLARIFY. |
| | 5) SHT.F-PP402 - 10" ST SHOWN ON SHEET F-PP402 BY |
| | ELEVATORS #1 & #2 BUT NOT ON F-PP110A. CLARIFY. |
| | 6) SHT. F-PP110A & SHT. F-PP110B SHOWS HUB DRAINS IN |
| | STAIRWELLS #1 & #2.THESE STAIRWELLS APPEAR TO BE RATED |
| | ENCLOSED STAIRS. THE HUB DRAINS ARE NOT PERMITTED IN |
| | THE STAIRWELLS PER THE 2010 FBC SEC.1022.4. |
| | 7) SHT. F-PP110A - PROVIDE A MATCH LINE REFERENCE AT |
| | THE BOTTOM OF THE PAGE SOUTH OF COLUMN LINE #8. WPB |
| | AMEND. TO 2010 FBC SEC. 107.2.1. |
| | 8) SHT.F-PP120A - SHOW THE DISCHARGE POINT OF THE 2" |
| | SANITARY PUMP LINE OR REFER TO THE DRAWING WHERE IT CAN |
| | BE FOUND. WPB AMEND. TO 2010 FBC SEC. 107.2.1. |
| | 9) SHT. F-PP401 - IDENTIFY THE AREAS ON THE CONDENSATE |
| | RISERS WHERE THEY ARE LOCATED, THE AHU'S ARE NOT SHOWN |
| | ON THE PLAN. DO THE SAME ON THE PLAN VIEWS. WPB AMEND. |
| | TO 2010 FBC SEC. 107.2.1. |
| | 10) SHT. F-PP401 - EXPAND THE SANITARY RISER FOR THE |
| | TOILET ROOM SO I CAN REVIEW IT. IT IS CRAMMED AND |
| | DIFFICULT TO READ. LABEL THE PLUMBING FIXTURES.WPB |
| | AMEND. TO 2010 FBC SEC. 107.2.1. |
| | 11) THE EJECTOR CONNECTION TO THE SANITARY SYSTEM SHALL |
| | CONNECT A MINIMUM OF 10 FEET FROM THE BASE OF ANY STACK |
| | PER 2010 FBC- PLUMBING SEC.712.3.5. |
| | 12) SHT. F-PP120B - COLUMN 12E NOTES 3/4" CW DN. BUT |
| | NOTHING IS SHOWN. CLARIFY. |
| | 13) SUBMIT A WATER RISER DIAGRAM FOR ALL THE WATER |
| | PIPING TO BE DONE. WPB AMEND. TO 2010 FBC SEC. |
| | 107.3.5.1.3. |
| | 14) ALL HUB DRAINS AND FLOOR DRAINS CONNECTED TO THE |
| | SANITARY SYSTEM SHALL BE EQUIPPED WITH TRAP PROIMERS |
| | PER 2010 FBC-PLUMBING SEC.100.2.4. THIS INCLUDES THE |
| | ONE S FOR THE ELEVATORS SUMPS. |
| | |
| | PLUMBING PLAN REVIEW |