| Plan Review Notes For Permit 15010651 |
| Permit Number |
15010651 |
|
| Review Stop |
FIRE |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2015-05-20 16:25:27 | THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC, | | | FIRE MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | | | THIS REVIEW APPROVAL IS FOR THE FOUNDATION ONLY. | | | | | | THE REQUIREMENT OF A FULL SPRINKLER SYSTEM ON ALL | | | FLOORS REMIANS UNDER REVIEW AND IS NOT APPROVED UNDER | | | THIS PERMIT. | | | | | | THE LIFE SAFETY GENERAL INFORMATION ON SHEET AS000 HAS | | | NOT BEEN FULLY REVIEWED AND/OR APPROVED BY FIRE | | | PREVENTION REGARDING "OPEN" OR "CLOSED" EXTERIOR WALL | | | OPENINGS. GREATER DETAIL AND EXPLANATION IS NEEDED FOR | | | THE EXTERIOR WALL COVERINGS AND THEIR COMPLIANCE WITH | | | THE REQUIREMENTS OF THE FLORIDA LIFE SAFETY CODE, NFPA | | | 101 CHAPTER 42, NFPA 88A AND IT'S A HIGHRISE BUILDING. | | | | | | PER NFPA 88A - | | | 5.5 OPENING REQUIREMENTS FOR OPEN PARKING STRUCTURES. | | | 5.5.1 EACH PARKING LEVEL SHALL HAVE WALL OPENINGS OPEN | | | TO THE | | | ATMOSPHERE, FOR AN AREA OF NOT LESS THAN 0.4 M2 FOR | | | EACH LINEAR | | | METER (1.4 FT2 FOR EACH LINEAR FOOT) OF ITS EXTERIOR | | | PERIMETER. | | | | | | PROVIDE DETAILS THAT THE PROPOSED DESIGN ON EACH TEIR | | | COMPLIES BEFORE AND THEN AFTER THE FACADE IS APPLIED. | | | | | | 5.5.2 SUCH OPENINGS SHALL BE DISTRIBUTED OVER 40 | | | PERCENT OF | | | THE BUILDING PERIMETER OR UNIFORMLY OVER TWO OPPOSING | | | SIDES. | | | | | | PROVIDE DEATILS THAT THE PROPOSED DESIGN ON EACH WALL | | | BEFORE AND THEN AFTER THE FACADE IS APPLIED. | | 2015-05-19 10:38:50 | NEW PLANS SUBMITTED. JG. |
|