| 2015-05-01 17:06:17 | ****CORRECTIONS**** |
| | ****REVISED 5/14/15*** |
| | |
| | SAMANTHA HILL |
| | BUILDING PLANS EXAMINER |
| | [email protected] |
| | 561-805-6724 |
| | EOR: THOMAS ROGERS, PE (ONM&J) |
| | ARCHITECT: WILLIAM A. HANSER (LEO A DALY) |
| | |
| | 1. INFORMATIONAL ONLY - A COPY OF THE THRESHOLD |
| | INSPECTION PLAN PREPARED BY THOMAS J. ROGERS, PE, |
| | ONM&J, HAS BEEN ROUTED TO KEN CONRAD, CHIEF BUILDING |
| | INSPECTOR. |
| | |
| | 2. INFORMATIONAL ONLY - AS THIS IS A THRESHOLD JOB, |
| | THREE SETS OF ALL DOCUMENTS REQUIRED. |
| | |
| | 3. NA |
| | |
| | 4. THRESHOLD DOCUMENTS PENDING K. CONRAD APPROVAL. |
| | |
| | PLEASE PROVIDE A RESUME FOR THE SUPERINTENDENT. ** |
| | |
| | 5. THE SOILS PROVIDED IS NOT AN ORIGINAL. ORIGINAL |
| | SIGNED, SEALED REPORTS ARE REQUIRED, FS471. |
| | |
| | THE SOILS HAS BEEN REVISED SINCE THE ENGINEER'S REVIEW |
| | (REFERENCE ON SHEET S7.1). PRIOR TO RESUBMITTAL, THE |
| | EOR IS TO REVIEW ALL SUBMITTALS INCLUDING THE |
| | GEOTECHNICAL REPORT, FBC 107. |
| | |
| | ** |
| | |
| | 6-7. OK |
| | |
| | 8A. FBC 705.8, SHOW LOCATION OF ASSUMED PROPERTY LINE |
| | (BETWEEN THE EXISTING CONVENTION CENTER AND PROPOSED |
| | PARKING GARAGE); PLEASE REVISE PLAN TO SHOW DISTANCE OF |
| | EACH BUILDING TO THE ASSUMED PROPERTY LINE (FBC 705.3) |
| | |
| | 2ND REVIEW; THIS WAS NOT PROVIDED. ARE THE TWO |
| | BUILDINGS TO BE CONSIDERED ONE LARGE BUILDING? IF THEY |
| | ARE TO BE CONSIDERED ONE BUILDING, PLEASE PROVIDE |
| | INFORMATION SHOWING COMPLIANCE WITH FBC TABLE 501. IF |
| | THEY ARE TWO BUILDINGS, ENOUGH INFORMATION FOR EACH |
| | BUILDING IS TO BE PROVIDED TO DEMONSTRATE COMPLIANCE |
| | WITH FBC 705.3. |
| | |
| | PROVIDE THE AREA OF THE PROPOSED GARAGE, FBC TABLE 501. |
| | |
| | 8B, SHEET AS000 INCLUDES ?MIXED USE OCCUPANCY HOUSING |
| | A?; PLEASE CLARIFY. SEE FBC CHAPTER 3. |
| | |
| | 8C, SHEET AS000 CITES SECTION 905.3 EXCEPTIONS 3 & 4 |
| | FOR SPRINKLERS; THIS SECTION IS FOR STANDPIPE |
| | REQUIREMENTS. PLEASE REVISE OR CLARIFY. |
| | |
| | ADVISORY ONLY; SPRINKLERS MAY BE REQUIRED FOR THE ROOF |
| | TOP CANOPY PER DISCUSSIONS WITH FIRE DEPT. THIS IS NOT |
| | REQUIRED TO BE ADDRESSED AT THIS TIME. |
| | |
| | 9-11. OK |
| | |
| | NEW COMMENTS: |
| | |
| | 12. EMAIL FROM CONTRACTOR WHICH CLARIFIES SCOPE UNDER |
| | THIS PERMIT STATES THAT A TEMPORARY SHEET PILE WILL BE |
| | INSTALLED. THIS IS SHOWN ON THE VIBROFLOTATION SITE |
| | PLAN BUT IS NOT SHOWN ANYWHERE IN THE PLAN PROVIDED. |
| | PROVIDE ALL INFORMATION REQUIRED TO INCORPORATE THE |
| | TEMPORARY SHEET PILES INTO THE SCOPE OF THIS PERMIT, |
| | FBC 107. |
| | |
| | 13. OK |
| | |
| | 14. PRIOR TO RESUBMITTING, PLEASE VERIFY THAT PLANS ARE |
| | COMPLETE. FOR INSTANCE; SHEETS S1A AND S2A REFER TO |
| | DETAIL 7 ON S9.3, BUT THAT SHEET WAS NOT PROVIDED (SEE |
| | S2A AT GRIDLINE A13). DETAIL 8 S9.1 LACKS THE STIRRUP |
| | SIZE. |
| | |
| | THE TRENCH DETAIL WAS PROVIDED, S9.1 SECTION 1, BUT THE |
| | WATERPROOFING INFORMATION WAS NOT PROVIDED (REFERS TO |
| | ARCHITECTURAL SHEETS, WHICH WERE NOT PROVIDED). ALSO |
| | PLEASE NOTE THAT THIS DETAIL DOES NOT SHOW A WATERSTOP; |
| | WATERPROOFING IS NOT CONTINUOUS TO PROTECT THE FOOTING |
| | FBC 1805.3.3. |
| | |
| | SEE ALSO COMMENTS FROM VIBROFLOTATION PERMIT |
| | APPLICATION 15031039 (IT IS NOT CLEAR AT THIS POINT |
| | WHETHER THIS WILL BE A SEPARATE PERMIT OR INCORPORATED |
| | INTO THIS FOUNDATION PERMIT): |
| | |
| | 15. FBC 3304.1, IT IS RECOMMENDED THAT CONTRACTOR |
| | ADVISE THE RESIDENTS ADJACENT TO PROPOSED CONSTRUCTION |
| | OF WORK PRIOR TO COMMENCEMENT. PROPERTY OWNERS IN THE |
| | ADJACENT TOWNHOUSES HAVE EXPRESSED CONCERN REGARDING |
| | THE STRUCTURAL IMPACT OF CONSTRUCTION AND CONTRACTOR |
| | HAS EXPLAINED HOW THIS WILL BE ADDRESSED, FBC 3307.1. |
| | PER CONTRACTOR, A STRUCTURAL ANALYSIS OF THE ADJACENT |
| | STRUCTURES WILL BE PERFORMED AND DOCUMENTED PRIOR TO |
| | CONSTRUCTION. |
| | |
| | IF THE ANALYSIS DISCUSSED IS NOT DONE PRIOR TO ISSUANCE |
| | OF THIS VIBROFLOTATION PERMIT, CONTRACTOR IS TO PROVIDE |
| | A LETTER STATING WHY THIS IS NOT NECESSARY AT THIS |
| | TIME. IT IS RECOMMENDED THAT CONTRACTOR PROVIDE |
| | INFORMATION REGARDING THE TIMING AND NATURE OF THIS |
| | PERMIT TO THE RESIDENTS PRIOR TO COMMENCEMENT. |
| | |
| | 16. ADVISORY ONLY - CONSTRUCTION HOURS ARE 7AM - 7PM |
| | MONDAY THROUGH FRIDAY; 8AM - 8PM WEEKENDS, CITY OF WEST |
| | PALM BEACH MUNICIPAL CODE SECTION 34-72. A WRITTEN |
| | EXCEPTION MAY BE GRANTED BY THE BUILDING OFFICIAL; |
| | PLEASE SUBMIT ANY SUCH REQUESTS (IF NEEDED) TIMELY TO |
| | [email protected], CC [email protected] AND [email protected]. |
| | |
| | 17. FOR ALL NEW SHEETS FOR THIS PERMIT AND ALL NEW |
| | SHEETS SUBMITTED ON OTHER RELATED PERMITS: |
| | |
| | A. INCLUDE THE ARCHITECT BUSINESS NUMBER ON EACH SHEET, |
| | FS481. |
| | B. CHANGE ADDRESS FROM "650 OKEECHOBEE BL" TO "1099 |
| | FLORIDA AVE." |
| | |
| | |
| | |
| | |
| | |
| | |