| 2015-02-12 09:51:06 | ****CORRECTIONS**** |
| | |
| | SAMANTHA HILL |
| | BUILDING PLANS EXAMINER |
| | [email protected] |
| | 561-805-6724 |
| | |
| | 1. INFORMATIONAL ONLY - A COPY OF THE THRESHOLD |
| | INSPECTION PLAN PREPARED BY THOMAS J. ROGERS, PE, |
| | ONM&J, HAS BEEN ROUTED TO KEN CONRAD, CHIEF BUILDING |
| | INSPECTOR. |
| | |
| | 2. INFORMATIONAL ONLY - AS THIS IS A THRESHOLD JOB, |
| | THREE SETS OF ALL DOCUMENTS REQUIRED. |
| | |
| | 3. INFORMATIONAL ONLY - IMPORTANT NOTICE: EFFECTIVE |
| | MARCH 2, 2015 |
| | |
| | ALL PERMIT APPLICATION PLAN REVIEWS WILL BE PERFORMED |
| | ELECTRONICALLY |
| | |
| | UPON APPLICATION AND FEE PAYMENT DESIGN DOCUMENTS |
| | SUBMISSION OPTIONS ARE AS FOLLOWS: |
| | |
| | 1 UPLOAD VIA THE PROJECTDOX PORTAL WITH DIGITAL |
| | SIGNATURES OF DESIGN PROFESSIONALS AS APPLICABLE; USE |
| | THE REQUIRED NAMING CONVENTION FOR EACH DOCUMENT |
| | 2 INCLUDE ON A CD WITH DESIGN PROFESSIONAL DIGITAL |
| | SIGNATURES AS APPLICABLE; USE THE REQUIRED NAMING |
| | CONVENTION FOR EACH DOCUMENT |
| | 3 INCLUDE ON A CD WITH ONE SET OF TRADITIONAL PAPER |
| | DESIGN DOCUMENTS SIGNED AND SEALED AS REQUIRED; USE THE |
| | REQUIRED NAMING CONVENTION FOR EACH DOCUMENT |
| | 4 ONE SET OF TRADITIONAL PAPER DESIGN DOCUMENTS SUBJECT |
| | TO ADMINISTRATIVE FEES TO DIGITIZE THE DOCUMENTS |
| | |
| | ADDITIONAL INFORMATION AND SPECIFIC PROCEDURES WILL BE |
| | SENT TO YOU WHEN AVAILABLE |
| | |
| | FOR THIS THRESHOLD JOB, CONTRACTOR IS RESPONSIBLE FOR |
| | PROVIDING A SET OF ALL DOCUMENTS TO THE SPECIAL |
| | INSPECTOR. |
| | |
| | 4. FS 553.79(5), FBC 2010 110.3.7.1, THE ENFORCING |
| | AGENCY SHALL REQUIRE A SPECIAL INSPECTOR TO PERFORM |
| | STRUCTURAL INSPECTIONS ON A THRESHOLD BUILDING PURSUANT |
| | TO A STRUCTURAL INSPECTION PLAN PREPARED BY THE |
| | ENGINEER OR ARCHITECT OF RECORD. PROVIDE A SPECIAL |
| | INSPECTOR AGREEMENT SIGNED BY ALL PARTIES. |
| | |
| | PROVIDE A RESUME OF INSPECTION EXPERIENCE AND COPIES OF |
| | ALL CERTIFICATES/LICENSES AS APPLICABLE FOR PROPOSED |
| | INSPECTORS. |
| | |
| | PLEASE FEEL FREE TO CONTACT ME OR KEN CONRAD, CHIEF |
| | BUILDING INSPECTOR, FOR MORE INFORMATION |
| | ([email protected], 561-805-6666). |
| | |
| | 5. PROVIDE THE GEOTECHNICAL REPORT REFERRED TO ON SHEET |
| | S7.1 (TIERRA SOUTH 7/15/14), FBC 2010 BUILDING 1803.5. |
| | |
| | 6. DOCUMENTS PREPARED BY AN ARCHITECT AND SUBMITTED FOR |
| | PUBLIC RECORD ARE TO BE SIGNED, SEALED, DATED ORIGINALS |
| | FS481. THE ARCHITECTURAL SHEETS ARE MARKED *FOR |
| | REFERENCE ONLY*. THE PAGES PROVIDED ARE REQUIRED |
| | INFORMATION TO OBTAIN A FOUNDATION PERMIT, FBC 107. |
| | |
| | 6. THRESHOLD BLDG, REQUIRED STATEMENT: |
| | |
| | W.P.B. AMENDMENT 109.3.6.4.4 ALL PLANS FOR THE BUILDING |
| | WHICH ARE REQUIRED TO BE SIGNED AND SEALED BY THE |
| | ARCHITECT OR ENGINEER OF RECORD CONTAIN A STATEMENT |
| | THAT, TO THE BEST OF THE ARCHITECT'S OR ENGINEER'S |
| | KNOWLEDGE, THE PLANS AND SPECIFICATIONS COMPLY WITH THE |
| | APPLICABLE FIRE-SAFETY STANDARDS AS DETERMINED BY THE |
| | LOCAL AUTHORITY IN |
| | ACCORDANCE WITH THIS SECTION AND 633 FLORIDA STATUTE. |
| | |
| | PLEASE INCLUDE THE THRESHOLD DESIGN COMPLIANCE |
| | STATEMENT ON THE ARCHITECTURAL SHEETS (ALREADY ON THE |
| | ENGINEERING SHEETS). |
| | |
| | 7. PLEASE INCORPORATE THE FOLLOWING ADVISORY NOTICE |
| | INTO THE PLAN: |
| | |
| | * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION |
| | 110.7 IMPACT OF CONSTRUCTION. ALL CONSTRUCTION ACTIVITY |
| | REGULATED BY THIS CODE SHALL BE PERFORMED IN A MANNER |
| | SO AS NOT TO ADVERSELY IMPACT THE CONDITION OF ADJACENT |
| | PROPERTY, UNLESS SUCH ACTIVITY IS PERMITTED TO AFFECT |
| | SAID PROPERTY PURSUANT TO A CONSENT GRANTED BY THE |
| | APPLICABLE PROPERTY OWNER, UNDER TERMS OR CONDITIONS |
| | AGREEABLE TO THE APPLICABLE PROPERTY OWNER. THIS |
| | INCLUDES, BUT IS NOT LIMITED TO, THE CONTROL OF DUST, |
| | NOISE, WATER OR DRAINAGE RUN-OFFS, DEBRIS, AND THE |
| | STORAGE OF CONSTRUCTION MATERIALS. NEW CONSTRUCTION |
| | ACTIVITY SHALL NOT ADVERSELY IMPACT LEGAL HISTORIC |
| | SURFACE WATER DRAINAGE FLOWS SERVING ADJACENT |
| | PROPERTIES, AND MAY REQUIRE SPECIAL DRAINAGE DESIGN |
| | COMPLYING WITH ENGINEERING STANDARDS TO PRESERVE THE |
| | POSITIVE DRAINAGE PATTERNS OF THE AFFECTED SITES. |
| | ACCORDINGLY, DEVELOPERS, CONTRACTORS AND OWNERS OF ALL |
| | NEW RESIDENTIAL DEVELOPMENT, INCLUDING ADDITIONS, |
| | POOLS, PATIOS, DRIVEWAYS, DECKS OR SIMILAR ITEMS, ON |
| | EXISTING PROPERTIES RESULTING IN A SIGNIFICANT DECREASE |
| | OF PERMEABLE LAND AREA ON ANY PARCEL OR HAS ALTERED THE |
| | DRAINAGE FLOW ON THE DEVELOPED PROPERTY SHALL, AS A |
| | PERMIT CONDITION, PROVIDE A PROFESSIONALLY PREPARED |
| | DRAINAGE PLAN CLEARLY INDICATING COMPLIANCE WITH THIS |
| | PARAGRAPH. UPON COMPLETION OF THE IMPROVEMENT, A |
| | CERTIFICATION FROM A LICENSED PROFESSIONAL SHALL BE |
| | SUBMITTED TO THE INSPECTOR IN ORDER TO RECEIVE APPROVAL |
| | OF THE FINAL INSPECTION. |
| | |
| | 8. ALTHOUGH LOCATION OF PROPOSED GARAGE RELATIVE TO LOT |
| | LINES AND EXISTING STRUCTURE APPEAR COMPLIANT, IT IS |
| | NOT POSSIBLE TO DETERMINE CODE COMPLIANCE WITHOUT THE |
| | INFORMATION REQUESTED BELOW. PLEASE REVISE PLAN TO |
| | INCLUDE THE FOLLOWING INFORMATION IN ORDER TO |
| | DEMONSTRATE COMPLIANCE WITH FBC 705.8: |
| | |
| | SHOW LOCATION OF ASSUMED PROPERTY LINE (BETWEEN THE |
| | EXISTING CONVENTION CENTER AND PROPOSED PARKING |
| | GARAGE); PLEASE REVISE PLAN TO SHOW DISTANCE OF EACH |
| | BUILDING TO THE ASSUMED PROPERTY LINE (FBC 705.3) |
| | |
| | BUILDING CONSTRUCTION TYPE (FBC 602) AND OCCUPANCY |
| | CLASSIFICATION OF EXISTING CONVENTION CENTER AND |
| | PROPOSED PARKING GARAGE |
| | |
| | SPRINKLER INFORMATION FOR EXISTING CONVENTION CENTER |
| | AND PROPOSED PARKING GARAGE (FBC TABLE 503) |
| | |
| | 9. SCOPE UNDER THIS FOUNDATION PERMIT PER CONTRACTOR |
| | INCLUDES VIBROFLOTATION, EXCAVATION OF LOWER LEVEL, |
| | CONCRETE WORK FOR FOOTINGS, ELEVATOR PITS, FOUNDATION |
| | WALL AND FIRST LIFT OF COLUMNS. A TRENCH DRAIN IS SHOWN |
| | ON S1B WITH A REFERENCE TO ARCHITECTURAL SHEETS, IS |
| | THIS ALSO IN THE SCOPE OF THIS PERMIT? IF INCLUDED, |
| | PROVIDE A DETAIL, FBC 107. IF NOT INCLUDED, DISREGARD |
| | COMMENT. |
| | |
| | 10. PLEASE PROVIDE COMPLIANCE IN CREATING A SECURE SITE |
| | AND IN COMPLIANCE WITH 3306.1 PROTECTION OF PEDESTRIANS |
| | AND 3306.5 AND 3306.6 BARRIERS. |
| | |
| | 11. SHEET S7.1, SEVERAL REFERENCE STANDARDS REFER TO |
| | *LATEST EDITION*. SEE FBC CHAPTER 35 AND REVISE TO |
| | INDICATE THE STANDARD VERSION USED FOR DESIGN. IF A |
| | STANDARD USED IN THE DESIGN OF THIS STRUCTURE IS NOT |
| | THE STANDARD SPECIFIED BY FBC CHAPTER 35, THIS SHOULD |
| | BE SUBMITTED USING FBC 104.11, ALTERNATIVE MATERIALS |
| | AND METHODS. PLEASE CONTACT ME IF YOU NEED FURTHER |
| | ASSISTANCE. |
| | |
| | |
| | |
| | |