| Date |
Text |
| 2015-02-26 15:27:13 | 6651 NORTH JOG ROAD - FIRE PUMPS DIESEL STORAGE TANKS |
| | PERMIT #15010629 |
| | REVIEW COMMENTS - FIRE DEPARTMENT |
| | |
| | NFPA 1 SECTION 66.22.5.2.4 STEEL SUPPORT STRUCTURES OR |
| | EXPOSED PILING FOR TANKS STORING CLASS I, CLASS II, OR |
| | CLASS IIIA LIQUIDS SHALL BE PROTECTED BY MATERIALS |
| | HAVING A FIRE RESISTANCE RATING OF NOT LESS THAN 2 |
| | HOURS. |
| | |
| | NFPA 1 SECTION 66.21.7.2.1 IDENTIFICATION FOR EMERGENCY |
| | RESPONDERS. A SIGN OR MARKING THAT MEETS THE |
| | REQUIREMENTS OF NFPA 704, STANDARD SYSTEM FOR THE |
| | IDENTIFICATION OF THE HAZARDS OF MATERIALS FOR |
| | EMERGENCY RESPONSE, OR ANOTHER APPROVED SYSTEM, SHALL |
| | BE APPLIED TO STORAGE TANKS CONTAINING LIQUIDS. THE |
| | MARKING SHALL BE LOCATED WHERE IT CAN BE SEEN, SUCH AS |
| | ON THE SIDE OF THE TANK, THE SHOULDER OF AN ACCESSWAY |
| | OR WALKWAY TO THE TANK OR TANKS, OR ON THE PIPING |
| | OUTSIDE OF THE DIKED AREA. IF MORE THAN ONE TANK IS |
| | INVOLVED, THE MARKINGS SHALL BE SO LOCATED THAT EACH |
| | TANK CAN BE IDENTIFIED. |
| | |
| | NFPA 1 SECTION 66.27.9 PIPING SYSTEMS SHALL BE BONDED |
| | AND GROUNDED. ANY ELECTRICALLY ISOLATED SECTION OF |
| | METALLIC PIPING OR EQUIPMENT SHALL BE BONDED AND |
| | GROUNDED TO PREVENT HAZARDOUS ACCUMULATION OF STATIC |
| | ELECTRICITY. |
| | |
| | NFPA 20 SECTION 11.4.2 FUEL LINE PROTECTION: A GUARD, |
| | PIPE PROTECTION, OR APPROVED DOUBLE-WALLED PIPE SHALL |
| | BE PROVIDED FOR ALL EXPOSED FUEL LINES. |
| | |
| | NFPA 20 SECTION 11.4.5.7 MEANS OTHER THAN SIGHT TUBES |
| | FOR CONTINUOUS INDICATING OF THE AMOUNT OF FUEL IN EACH |
| | STORAGE TANK SHALL BE PROVIDED. |
| | |
| | NFPA 20 SECTION 11.4.7.4 THE GRADE OF FUEL OIL SHALL BE |
| | INDICATED ON THE FUEL TANK BY LETTERS THAT ARE A |
| | MINIMUM OF 6-INCHES IN HEIGHT AND IN CONTRASTING COLOR |
| | TO THE TANK. |
| | |
| | NFPA 20 SECTION 11.6.4.1 THE FUEL STORAGE TANKS SHALL |
| | BE KEPT AS FULL AS PRACTICAL AT ALL TIMES, BUT NEVER |
| | BELOW 66 PERCENT (TWO-THIRDS) OF TANK CAPACITY. A FUEL |
| | LEVEL INDICATOR ON THE FIRE PUMP CONTROLLER SHALL BE |
| | PROVIDED TO ACTIVATE AT THE TWO-THIRDS TANK LEVEL. |
| | |
| | WESLEY JOLIN |
| | ASSISTANT FIRE MARSHAL |
| | FIRE INVESTIGATOR & INSPECTOR |
| | OFFICE OF THE FIRE MARSHAL |
| | WEST PALM BEACH FIRE RESCUE |
| | [email protected] |
| | (561) 805-6730 |
| | |
| | |