2015-04-10 14:37:52BUILDING REVIEW APPROVED WITH PROVISO:
  
 1- FLAT ROOF: ENGINEER TO REVISE THE RAS 117
 CALCULATIONS. NAIL SPACING SHOWN FOR ROOF ZONE #1
 DOESN'T MATCH NAIL SPACING SHOWN ON NOA 13-1022.15.
 REVISE ALL CALCULATIONS AS REQUIRED. SEE SEC. 8.1 OF
 RAS 117.
 2- REVISE ALL NOTES ON SHEET SP-1. THIS IS A NEW SINGLE
 FAMILY RESIDENCE NOT REMODELING. EXISTING HOUSE WILL BE
 COMPLETELY DEMOLISHED.
 3- REVISE TYP. WALL SECTION 1/A-2. ATTIC VENTED OR
 ICYNENE INSULATION. COORDINATE WITH THE ENERGY
 CALCULATIONS.
 4- PROVIDE ICYNENE ICC EVALUATION REPORT (2 COPIES).
 5- PROVIDE PRODUCT APPROVAL (2 COPIES) FOR ALL SIMPSON
 STRUCTURAL CONNECTORS SPECIFIED ON ALL PLANS AND
 DETAILS OR SPECIFY THE FLORIDA PRODUCT APPROVAL NUMBER
 NEXT TO THE SPECIFIED CONNECTOR. ALSO, UPDATE THE
 FLORIDA PRODUCT APPROVAL NUMBERS SPECIFIED ON CONNECTOR
 SCHEDULE ON SHEET S-2. THEY DON'T CORRESPOND TO THE
 2010 FBC CODE VERSION.
  