2015-03-05 14:07:30GAF CONVENTIONAL BUILT UP ROOF SYSTEM NOA 13-1022.15
 SUBMITTED:
  
 A) CLEARLY IDENTIFY WHICH APPROVED ASSEMBLY IS GOING TO
 BE INSTALLED TO VERIFY COMPLIANCE WITH SEC. R301 OF
 2010 FBC.
  
 B) PROVIDE SIGNED AND SEALED RAS 117 CALCULATIONS AS
 REQUIRED BY GENERAL LIMITATION $7 ON LAST PAGE OF NOA.
 NEED THE NAIL ENHANCING CALCULATIONS TO MEET THE DESIGN
 PRESSURES REQUIRED BY SEC. R301.
  