| Plan Review Notes For Permit 15010607 |
| Permit Number |
15010607 |
|
| Review Stop |
R |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2015-03-05 14:07:30 | GAF CONVENTIONAL BUILT UP ROOF SYSTEM NOA 13-1022.15 | | | SUBMITTED: | | | | | | A) CLEARLY IDENTIFY WHICH APPROVED ASSEMBLY IS GOING TO | | | BE INSTALLED TO VERIFY COMPLIANCE WITH SEC. R301 OF | | | 2010 FBC. | | | | | | B) PROVIDE SIGNED AND SEALED RAS 117 CALCULATIONS AS | | | REQUIRED BY GENERAL LIMITATION $7 ON LAST PAGE OF NOA. | | | NEED THE NAIL ENHANCING CALCULATIONS TO MEET THE DESIGN | | | PRESSURES REQUIRED BY SEC. R301. | | | |
|