| 2015-03-05 14:30:29 | RESIDENTIAL (R3) ADDITION/ALTERATION MECHANICAL REVIEW |
| | COMMENTS. |
| | CODE: 2010 FBC. |
| | |
| | 1- EQUIPMENT SIZING CALCULATIONS: |
| | A) REVISE THE EQUIPMENT SIZING CALCULATIONS. |
| | CALCULATIONS WERE DONE TRANSFERRING THE INFORMATION |
| | FROM THE ENERGY CALCULATIONS. ENERGY CALCULATIONS WERE |
| | DONE BASED ON THE WORST CASE SCENARIO. A/C EQUIPMENT |
| | SIZING CALCULATIONS CAN NOT BE DONE BASED ON THE WORST |
| | CASE SCENARIO. THEY NEED TO BE DONE BASED ON THE |
| | BUILDING LOADS FOR THE DIRECTIONAL ORIENTATION OF THE |
| | BUILDING AS REQUIRED BY SEC. 403.6.1 OF 2010 FBC-ENERGY |
| | CONSERVATION. REVISE AS REQUIRED. |
| | |
| | B) REVISE THE OVERHANG LENGTH AND OVERHANG HEIGHT TO |
| | MATCH PLANS. SEC. 103.2.2 OF 2010 FBC-ENERGY |
| | CONSERVATION |
| | |
| | C) HOUSE ATTIC WAS DESIGNED AS VENTED NOT UNVENTED. SEE |
| | PLANS AND REVISE AS REQUIRED. SEC. 103.2.2 OF 2010 |
| | FBC-ENERGY CONSERVATION |
| | |
| | D) REVISE NUMBER OF OCCUPANTS. THERE ARE NOT 10 |
| | OCCUPANTS AND 32 OCCUPANTS IN A 3 BEDROOM SINGLE FAMILY |
| | RESIDENCE. SEC. 103.2.2 OF 2010 FBC-ENERGY CONSERVATION |
| | |
| | 2- PROVIDE THE NAME AND SIGNATURE OF THE PERSON |
| | RESPONSIBLE FOR THE DESIGN ON THE A/C PLAN AS REQUIRED |
| | BY SEC. 107.2.1 OF CITY AMENDMENTS TO FBC. |
| | |
| | ***PLEASE PROVIDE LETTER ADDRESSING EACH COMMENT TO |
| | HELP EXPEDITE THE REVIEW PROCESS. |
| | ***PLEASE REMOVE AND REPLACE EACH REVISED SHEET. |
| | |