| | PROJECT: JAMES BROOKS RESIDENCE |
| | PERMIT#: 15010607 |
| | CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC |
| | ,2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1, |
| | ADMINISTRATION, 2012 FBC SUPPLEMENTS. |
| | 1ST ELECTRICAL PLAN REVIEW |
| | ACTION: DENIED |
| | |
| | 1) REVISE THE RISER DIAGRAM TO INDICATE THE FEEDER TO |
| | THE POOL PANEL. NEC 215.5 |
| | |
| | 2) PROVIDE A PANEL SCHEDULE FOR BOTH PANELS NEC 408.4 |
| | |
| | 3) REVISE GROUNDING ELECTRODE SYSTEM TO INCLUDE TWO |
| | DRIVEN GROUND RODS AND A INTERSYSTEM BOND BAR. NEC |
| | 250.50 AND 250.94 |
| | |
| | 4) ALL OUTLETS IN THE GARAGE INCLUDING THOSE FOR THE |
| | GARAGE DOOR OPENERS SHALL BE GFI PROTECTED. NEC 210.8 |
| | |
| | 5) PROVIDE A FAULT CURRENT CALCULATION TO VERIFY THE |
| | ELECTRICAL SERVICE DISCONNECTING MEANS HAS A FAULT |
| | CURRENT RATING THAT IS SUFFICIENT FOR THE CURRENT THAT |
| | MUST BE INTERRUPTED. NEC 110.9 |
| | |
| | 6) PROVIDE ARC FAULT CIRCUIT INTERUPTER PROTECTION ON |
| | ALL BRANCH CIRCUITS AS REQUIRED. NEC 210.12 |
| | |
| | 7) ALL NEW GENERAL PURPOSE OUTLETS MUST BE TAMPER |
| | RESISTANT AND AFCI PROTECTED. NEC 210.12, 406.11 |
| | |
| | 8) BOXES LISTED SPECIFICALLY FOR THIS APPLICATION SHALL |
| | BE USED FOR RECEPTACLES LOCATED IN THE FLOOR. NEC |
| | 314.27(C) |
| | |
| | 9) PROVIDE PRODUCT APPOVALS FOR JACUZZI TUB. GFI |
| | REQUIRED. NEC 680.71 |
| | |
| | 10) SEPARATE PERMIT APPLICATIONS ACCOMPANIED BY |
| | MANUFACTURERS EQUIPMENT SUBMITTALS, AND SHOP DRAWINGS |
| | ARE REQUIRED FOR SITE LIGHTING, AUDIO/VIDEO SYSTEM, |
| | SECURITY, AND CCTV.. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. SEE LINK: |
| | HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/ |
| | 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF |
| | |
| | ADDITIONALLY, IT IS REQUIRED TO INSERT THE CORRECTED |
| | PAGES INTO THE DENIED SUBMITTAL PACKAGE. VOID THE |
| | PREVIOUSLY REVIEWED SHEETS AND LEAVE FOR COMPARATIVE |
| | REVIEW. |
| | |
| | DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421, |
| | 561-805-6717 OR [email protected] |
| | |