| 2015-01-20 13:36:57 | 1/20/2015 |
| | PROJECT: BOA ADA COMPLIANCE |
| | PERMIT#: 15010581 |
| | CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC |
| | ,2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1, |
| | ADMINISTRATION, 2012 FBC SUPPLEMENTS. |
| | 1ST ELECTRICAL PLAN REVIEW |
| | ACTION: DENIED |
| | |
| | 1) A SEPARATE ELECTRICAL PERMIT APPLICATION IS REQUIRED |
| | FOR THE ELECTRICAL SCOPE OF THIS PROJECT.. |
| | |
| | 2) PROVIDE ELECTRICAL PLANS AND SPECIFICATIONS TO |
| | INDICATE COMPLIANCE WITH THE FBC-ENERGY 505.2 AND THE |
| | NEC 422.52 FOR THE GFCI PROTECTED RECEPTACLE OUTLET AT |
| | THE DRINKING FOUNTAIN. |
| | |
| | 3) PROVIDE A LIGHTING FIXTURE PLAN INDICATING AND NEW |
| | FIXTURES, RELOCATED FIXTURES AND ASSOCIATED SWITCHES OR |
| | LIGHTING CONTROLS, AND EXISTING FIXTURES TO REMAIN. WPB |
| | AMENDMENTS TO FBC 107.3 |
| | |
| | 4) INCLUDE EMERGENCY AND EXIT LIGHTING ON THE ELECRICAL |
| | LIGHTING PLAN TO INDICATE COMPLIANCE WITH NEC 700.12(F) |
| | AND 700.16. |
| | |
| | 5) NOTES ON SHEET A00.00 CALL FOR WORK TO COMPLY WITH |
| | GOVERNING CODES, THEN CALLS OUT THE 2011 EDITION OF THE |
| | NATIONAL ELECTRICAL CODE. THE 2008 EDITION IS CURENTLY |
| | IN EFFECT. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. SEE LINK: |
| | HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/ |
| | 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF |
| | |
| | ADDITIONALLY, IT IS REQUIRED TO INSERT THE CORRECTED |
| | PAGES INTO THE DENIED SUBMITTAL PACKAGE. VOID THE |
| | PREVIOUSLY REVIEWED SHEETS AND LEAVE FOR COMPARATIVE |
| | REVIEW. |
| | |
| | DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421, |
| | 561-805-6717 OR [email protected] |
| | |