2015-01-20 13:36:571/20/2015
 PROJECT: BOA ADA COMPLIANCE
 PERMIT#: 15010581
 CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC
 ,2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1,
 ADMINISTRATION, 2012 FBC SUPPLEMENTS.
 1ST ELECTRICAL PLAN REVIEW
 ACTION: DENIED
  
 1) A SEPARATE ELECTRICAL PERMIT APPLICATION IS REQUIRED
 FOR THE ELECTRICAL SCOPE OF THIS PROJECT..
  
 2) PROVIDE ELECTRICAL PLANS AND SPECIFICATIONS TO
 INDICATE COMPLIANCE WITH THE FBC-ENERGY 505.2 AND THE
 NEC 422.52 FOR THE GFCI PROTECTED RECEPTACLE OUTLET AT
 THE DRINKING FOUNTAIN.
  
 3) PROVIDE A LIGHTING FIXTURE PLAN INDICATING AND NEW
 FIXTURES, RELOCATED FIXTURES AND ASSOCIATED SWITCHES OR
 LIGHTING CONTROLS, AND EXISTING FIXTURES TO REMAIN. WPB
 AMENDMENTS TO FBC 107.3
  
 4) INCLUDE EMERGENCY AND EXIT LIGHTING ON THE ELECRICAL
 LIGHTING PLAN TO INDICATE COMPLIANCE WITH NEC 700.12(F)
 AND 700.16.
  
 5) NOTES ON SHEET A00.00 CALL FOR WORK TO COMPLY WITH
 GOVERNING CODES, THEN CALLS OUT THE 2011 EDITION OF THE
 NATIONAL ELECTRICAL CODE. THE 2008 EDITION IS CURENTLY
 IN EFFECT.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. SEE LINK:
 HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/
 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF
  
 ADDITIONALLY, IT IS REQUIRED TO INSERT THE CORRECTED
 PAGES INTO THE DENIED SUBMITTAL PACKAGE. VOID THE
 PREVIOUSLY REVIEWED SHEETS AND LEAVE FOR COMPARATIVE
 REVIEW.
  
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]
  