2015-01-25 06:06:031) THE VENT FOR THE MOP SINK MUST BE WASHED BY THE
 FIXTURE. DRY VENTS ARE PROHIBITED PER 2010 FL. PLBG.
 CODE SEC.905.3.;
 2) SHT. P-2 - THE GREASE WASTE RISER REFERS TO SHT. U-1
 FOR THE GREASE TRAP LOCATION. THE DRAWING IS NOT
 INCLUDED.SUBMIT THE DRAWING FOR REVIEW.WPB AMEND. TO
 2010 FBC SEC.107.2.1.
 3) THE DRINKING FOUNTAIN SHALL BE A HI-LO UNIT PER THE
 FAC SEC.211.2 & FL. EXISTING BUILDING CODE SEC. 706.1.
  