| Plan Review Notes For Permit 15010560 |
| Permit Number |
15010560 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2015-01-25 06:06:03 | 1) THE VENT FOR THE MOP SINK MUST BE WASHED BY THE | | | FIXTURE. DRY VENTS ARE PROHIBITED PER 2010 FL. PLBG. | | | CODE SEC.905.3.; | | | 2) SHT. P-2 - THE GREASE WASTE RISER REFERS TO SHT. U-1 | | | FOR THE GREASE TRAP LOCATION. THE DRAWING IS NOT | | | INCLUDED.SUBMIT THE DRAWING FOR REVIEW.WPB AMEND. TO | | | 2010 FBC SEC.107.2.1. | | | 3) THE DRINKING FOUNTAIN SHALL BE A HI-LO UNIT PER THE | | | FAC SEC.211.2 & FL. EXISTING BUILDING CODE SEC. 706.1. | | | | | | PLUMBING PLAN REVIEW | | | TIM LARGE | | | CHIEF PLUMBING INSPECTOR | | | 561-805-6692 | | | [email protected] | | | |
|