Plan Review Notes
Plan Review Notes For Permit 15010560
Permit Number 15010560
Review Stop B
Sequence Number 1
Notes
Date Text
2015-01-24 10:29:16BUILDING PLAN REVIEW
 REVISION: 15010560
 PERMIT: 14110435
 ADD: 1270 PALM BEACH LAKES
 CONT: EVANS PETROLEUM
 TEL: (305)796-9695
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: SAT. / JAN. 24/ 2015
 ACTION: DENIED
  
 1) SHEET A-1 DOES NOT PROVIDE DETAILS OF THE SODA
 FOUNTAINS, HOT OPTIONS OR HOT DOG ROTESSERIES FOR REACH
 RANGES NOR IF SIDE APPROACH OR FRONTAL APPROACH. NOTE
 THE PLANS DO INDICATE A 34 INCH COUNTER.
  
 2010 FBC-ACCESSIBILITY 308 REACH RANGES
 308.2 FORWARD REACH
 308.3 SIDE REACH
  
 309 OPERABLE PARTS
 309.1 GENERAL. OPERABLE PARTS SHALL COMPLY WITH 309.
 309.2 CLEAR FLOOR SPACE. A CLEAR FLOOR OR GROUND SPACE
 COMPLYING WITH 305 SHALL BE PROVIDED.
 309.3 HEIGHT. OPERABLE PARTS SHALL BE PLACED WITHIN ONE
 OR MORE OF THE REACH RANGES SPECIFIED IN 308.
 309.4 OPERATION. OPERABLE PARTS SHALL BE OPERABLE WITH
 ONE HAND AND SHALL NOT REQUIRE TIGHT GRASPING,
 PINCHING, OR TWISTING OF THE WRIST.
  
 A THOROUGH REVIEW CAN NOT BE MADE AT THIS TIME, AS A
 RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved