Plan Review Notes
Plan Review Notes For Permit 15010524
Permit Number 15010524
Review Stop P
Sequence Number 1
Notes
Date Text
2015-01-25 07:58:021) SUBMIT SPECIFICATIONS FOR THE MOP SINK. SEE
 SHT.A6.1, DETAIL #6. THIS DETAIL CONFLICTS WITH THE MOP
 SINK DETAI ON SHT.P-1, CLARIFY.
 2) SHT.A6.1 - ELEVATION "C"- SHOW THE SPACING OF THE
 REAR GRAB BAR TO COMPLY W/2010 FAC SEC.604.5.2.
 3) SIZE THE VENT FOR THE MOP SINK ON SHT. P-1.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  