| Plan Review Notes For Permit 15010524 |
| Permit Number |
15010524 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2015-02-03 08:43:50 | 1) VERIFY THE ELECTRICAL SERVICE DISCONNECTING MEANS | | | HAS A FAULT CURRENT RATING THAT IS SUFFICIENT AT | | | NOMINAL CIRCUIT VOLTAGE FOR THE CURRENT THAT MUST BE | | | INTERRUPTED. NEC 110.9 | | | | | | 2) PROVIDE SAFETY LABELING FOR ARC FLASH PROTECTION FOR | | | THE PANEL BOARDS AND MAIN DISCONNECTING MEANS. NEC | | | 110.16, 110.22 | | | | | | DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421, | | | 561-805-6717 OR [email protected] |
|