| Plan Review Notes For Permit 15010518 |
| Permit Number |
15010518 |
|
| Review Stop |
B |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2015-01-28 10:24:46 | RESIDENTIAL (R2) ALTERATION, BUILDING REVIEW COMMENTS. | | | CODE: 2010 FBC. | | | | | | 1- ACOUSTICORK UNDERLAYMENT: PROVIDE COPIES OF THE | | | SOUND TRANSMISSION CLASS (STC) TEST DONE IN ACCORDANCE | | | WITH ASTM E 90 AND IMPACT INSULATION CLASS (IIC) TESTS | | | DONE IN ACCORDANCE TO ASTM E 492. SEC. 1207.2 AND | | | 1207.3 OF 2010 FBC-BUILDING. | | | | | | NOTE: ASSEMBLY TESTED NEED TO MATCH CONDITIONS OF | | | PROPOSED FLOOR ASSEMBLY. TESTING SUBMITTED IS FOR WOOD | | | FLOOR ASSEMBLIES. ACCORDING TO CITY RECORDS THE FLOOR | | | BETWEEN APARTMENTS IS 7" CONCRETE SLAB WITH NO | | | SUSPENDED CEILING ASSEMBLY. THIS IS THE KIND OF | | | ASSEMBLY THE TESTING IS REQUIRED. | | | | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT | | | JULIO GOMEZ | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | DEVELOPMENT SERVICES DEPARTMENT | | | (561)805-6712 | | | [email protected] |
|