Plan Review Notes
Plan Review Notes For Permit 15010465
Permit Number 15010465
Review Stop B
Sequence Number 2
Notes
Date Text
2015-03-11 07:52:34BUILDING PLAN REVIEW
 PERMIT: 15010465
 ADD: 3762 JOG RD.
 CONT: MKS CONSTRUCTION
 TEL: (561)601-6146
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 1ST REVIEW
 DATE: THURS. JAN. 29/2015
 ACTION: DENIED
  
 12) CONTRACTOR TO PUT INNEW SHEETS, REMOVE OLD SHEETS.
 !!!!!!! WHEN RESUBMITTING PLANS PLEASE INDICATE THE
 REVISION & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES
 AS NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 1) 2ND REQUEST. THE SHEET S-1 DOES NOT PROVIDE WHATTHE
 MINIMUM SAFE BEARING VALUE OF THE SOILS. 2010 FBC-B
 1803.5.2 QUESTIONABLE SOIL.
 WHERE THE CLASSIFICATION, STRENGTH OR COMPRESSIBILITY
 OF THE SOIL IS IN DOUBT OR WHERE A LOAD-BEARING VALUE
 SUPERIOR TO THAT SPECIFIED IN THIS CODE IS CLAIMED, THE
 BUILDING OFFICIAL SHALL BE PERMITTED TO REQUIRE THAT A
 GEOTECHNICAL INVESTIGATION BE CONDUCTED.
  
 2) COMPLIED. SHEET S-1 SECTION A-A SHOWS THE BOTTOM OF
 THE FOUNDATION ONLY 6 INCHES BELOW GRADE. 1809.4 DEPTH
 AND WIDTH OF FOOTINGS.
 THE MINIMUM DEPTH OF FOOTINGS BELOW THE UNDISTURBED
 GROUND SURFACE SHALL BE 12 INCHES (305 MM). WHERE
 APPLICABLE, THE REQUIREMENTS OF SECTION 1809.5 SHALL
 ALSO BE SATISFIED. THE MINIMUM WIDTH OF FOOTINGS SHALL
 BE 12 INCHES (305 MM).
  
 3) COMPLIED. THE PLANS DO NOT SHOW COMPLIANCE WITH 2010
 FBC-B 1816.1 TERMITE PROTECTION. 1816.1.4 IF SOIL
 TREATMENT IS USED FOR SUBTERRANEAN TERMITE PREVENTION,
 CHEMICALLY TREATED SOIL SHALL BE PROTECTED WITH A
 MINIMUM 6 MILLIMETER VAPOR RETARDER TO PROTECT AGAINST
 RAINFALL DILUTION. IF RAINFALL OCCURS BEFORE VAPOR
 RETARDER PLACEMENT, RETREATMENT IS REQUIRED. ANY WORK,
 INCLUDING PLACEMENT OF REINFORCING STEEL, DONE AFTER
 CHEMICAL TREATMENT UNTIL THE CONCRETE FLOOR IS POURED,
 SHALL BE DONE IN SUCH MANNER AS TO AVOID PENETRATING OR
 DISTURBING TREATED SOIL. ALSO SEE 1910.1.
  
 4) COMPLIED. THE PLANS DO NOT INDICATE WHAT WILL BE
 USED TO RE-INFORCE THE MONOLITHIC SLAB WIRE MESH OR
 FIBER CONCRETE. 2010 FBC-B 1910.1 MINIMUM SLAB
 PROVISONS.
  
 5) SEMI-COMPLIED. SHEET S1 THE ROOF FRAMING PLAN A-A
 PROVIDES DETAILS THAT THIS IS A HAND FRAMED ROOF. THE
 PLANS SHOW 2X8 RIDGE AND 2X4 BENEATH THE RIDGE ON EACH
 END. THIS DETAIL ALSO SHOWS A LUS 24 AT THE CONNECTION
 OF THE RIDGE BEAM TO THE VERTICAL STUD. THIS DETAIL
 DOES NOT SHOW HOW THE VERTICAL STUD WILL BE ANCHORED TO
 THE BEAM, THIS IS PART OF THE MWFRS MAINWIND FORCE
 RESISTING SYSTEM. THERE IS NO NOTE AS ON THE GABLE END
 THE STUD PLACEMENT NOR THE ANCHORING OF THE GABLE END
 WALL SYSTEM.
  
 6) 2ND REQUEST. SHEET S1 ROOF FRAMING PLAN THERE IS NO
 SECTION FOR THE GABLE END WALL FRAMING OR IF THIS WILL
 BE A GABLE END TRUSS, PROVIDE DETAIL AND ANCHORAGE TO
 THE BOND BEAM PART OF THE MWFRS MAIN WIND FORCE
 RESISTING SYSTEM. 2010 FBC-B 1609.6.4 DESIGN PROCEDURE.
  
 7) COMPLIED. THERE IS ONLY ONE SET OF PRODUCT APPROVALS
 SUBMITTED FOR THIS PROJECT, 2 SETS ARE REQUIRED, ONE
 FOR THE FIELD INSPECTORS THE OTHER FOR THE CITY FILES
 RECORD RETENSION.
 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING
 CODE, CHAPTER 1, ADMINISTRATION,107.3.5 MINIMUM PLAN
 REVIEW CRITERIA FOR BUILDINGS.
  
 8) COMPLIED. 2010 FBC 107.3.4.1 PRODUCT APPROVALS.
 THOSE PRODUCTS WHICH ARE REGULATED BY THE DCA RULE
 9N-03 SHALL BE REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC..
  
 9) SEMI-COMPLIED. THE SUBMITTAL FOR BERTHA H. V.
 ACCORDIAN SHUTTERS NEEDS TO IDENTIFY THE FOLLOWING : FL
 BLD CODE 2010 SECTION 107.2.5.,
 1609.1.2, 1715.8 & EXIST BUILD CODE 606.4 PROCEDURES: A
 COMPLETE INSTALLATION SCHEDULE SUMMARIZING &
 IDENTIFYING OPENING SIZES, STORY HEIGHTS, UNIT MARK
 NUMBERS, UNIT SPANS/WIDTHS, UNIT STORM BAR REINFORCING
 REQUIREMENTS, WALL PRESSURE ZONES, SLAT TYPES, ETC.,
 SHALL BE SUBMITTED AT TIME OF PERMIT APPLICATION TO
 FACILITATE PLAN REVIEW AND PERMIT ISSUANCE.
  
  
 10) THE ROOFING PRODUCT APPROVAL SUBMITTED NOA
 11-0510.02 ENTEGRA ESTATE S TILE ATTACHMENT POLYFOAM
 POLYPRO PRODUCT APPROVAL WAS NOT SUBMITTED.
 UNDERLAYMENT SHALL BE APPLIED ACCORDING TO THE TILE
 MANUFACTURER'S INSTALLATION INSTRUCTIONS OR THE
 RECOMMENDATIONS OF THE FRSA/TRI 07320 WHERE THE BASIC
 WIND SPEED, VASD, IS DETERMINED IN ACCORDANCE WITH
 SECTION 1609.3.1 OR THE RECOMMENDATIONS OF RAS 118, 119
 OR 120.
  
 1507.3.2 DECK SLOPE.
 CONCRETE AND CLAY ROOF TILE SHALL BE INSTALLED IN
 ACCORDANCE WITH THE RECOMMENDATIONS OF FRSA/TRI 07320
 WHERE THE VASD AS DETERMINED IN ACCORDANCE WITH SECTION
 1609.3.1 OR THE RECOMMENDATIONS OF RAS 118, 119 OR 120.
  
 11) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  