| Plan Review Notes For Permit 15010463 |
| Permit Number |
15010463 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2015-01-29 11:30:15 | 1. FBC 107.3.5.3. PROVIDE PANEL SCHEDULE AND CIRCUITRY | | | FOR OUTLETS ON PLANS. | | | 2. N.E.C. 210.11(C)1. IDENTIFY A MININUM OF TWO SMALL | | | APPLIANCE CIRCUITS SUPPLYING KITCHEN COUNTERTOP | | | RECEPTACLES. | | | 3. FBC SECTION R314 LOCATION OF SMOKE ALARMS | | | 4. N.E.C. 210.12 ARC FAULT PROTECTION FOR OUTLETS ON 15 | | | AND 20 AMPERE BRANCH CIRCUITS FOR AREAS SPECIFIED IN | | | THIS CODE SECTION,(T.V. ENTERTAINMENT AREA.) | | | 5. N.E.C. 406.11 TAMPER RESISTANT RECEPTACLES. |
|