| 2015-04-09 06:14:21 | 1) SHT. P.5.2 - THE RAINWATER RISER FOR THE SHOWROOM |
| | AREA DOES NOT MATCH THE PLAN VIEW ON P2.1.1. ONE |
| | SECTION SHOWS A WYE CONNECTION ABOVE GROUND AND THE |
| | RISER SPLITTING INTO TWO HORIZONTAL BRANCES ON THE PLAN |
| | VIEW ON P2.1.1 AND THE SAME SECTION IS SHOWN AS ONE |
| | LINE RISING UP AND COLLECTING 4 ROOF DRAINS. CLARIFY. |
| | 2) SHT. P2.1.2.- THERE ARE TWO 4" RAINWATER BRANCHES |
| | THAT JUST END AND HAVE NO CONNECTION TO ROOF DRAINS OR |
| | SHOW A NOTE DETAILING CONTINUATION POINTS. THESE LINES |
| | ARE LOCATED IN THE PARTS AREA #135. I HAVE HIGHLIGHTED |
| | AND CLOUDED THE AREA IN RED. ONE TERMINATES NEAR GRID |
| | LINE G-2.2 AND THE OTHER IS BY GRID LINE F-1 BY STAIR |
| | #2. CLARIFY. 2ND REQUEST. |
| | 3) SHT.P2.1.3. - THE TRANSAIR ALUMINUM PIPE THAT IS |
| | CALLED OUT ON THE PLAN IS SHOWN AS BEING INSTALLED |
| | UNDERGROUND. I HAVE RESEARCHED THE PIPNG AND IT APPEARS |
| | IT MAY ONLY BE APPROVED FOR ABOVE GROUND INSTALLATION. |
| | SUBMIT VERIFICATION FROM THE MANUFACTURER THAT IT IS |
| | APPROVED FOR UNDERGROUND INSTALLATION. THIS CAN BE A |
| | DEFERRED SUBMITTA.WPB AMEND. TO 2010 FBC SEC. 107.2.1. |
| | 4) SHT. P2.1.1 REFERS TO 1" CONDENSATE PIPE AND PUMP |
| | ABOVE CEILING BUT THERE IS NOTHING SHOWN. I HAVE |
| | HIGHLIGHTED THE AREA OF ISSUE.THERE IS A NOTE THAT ALSO |
| | STATES" SEE SHT. P2.1.2 FOR CONTINUATION" BUT NOTHING |
| | IS SHOWN ON SHT. P2.1.2.CLARIFY. 2ND REQUEST. |
| | 5) SHT.P2.1.2. - SHOWS A 3" RAINWATER LEADER IN STAIR |
| | ENCLOSURE # 3 AND ALSO IN STAIR #1 . I HAVE REVIEWED |
| | YOUR RESPONSE TO MY COMMENT. THE ARCHITECT OF RECORD |
| | HAS RATED BOTH OF THESE ENTIRE ENCLOSURES AS ONE HOUR |
| | ON SHT.A-001. THE RAINWATER PIPING CANNOT PENETRATE ANY |
| | WALLS OF THESE RATED ENCLOSURES PER 2010 FBC 1022.4. |
| | THIS CODE SECTION DOES NOT JUST APPLY TO ADJACENT |
| | SPACES OR ENCLOSURES.IF THE 3" RAINWATER RISER ENTERS |
| | THE ENCLOSURES FROM UNDERGROUND THROUGH THE GROUND |
| | FLOOR SLAB OF THE ENCLOSURE, THEN THERE IS NOT AN ISSUE |
| | BUT THAT IS NOT WHAT THE RAINWATER RISER ON SHT. P5.2 |
| | DEPICTS OR THE PLAN VIEWS ON P2.1.1 OR P2.1.2. IF THIS |
| | IS SUCH THE CASE, THEN CLEARLY IDENTIFY THIS ON BOTH |
| | SHEETS. SHT. 5.2 SHOWS THIS 3" LINE CONNECTING TO THE |
| | STORM DRAIN LINE BELOW THE ROOF SLAB, NOT UNDERGROUND. |
| | CLARIFY. |
| | |