| 2015-03-25 15:24:50 | 1) SUBMIT A RISER DIAGRAM FOR THE RAINWATER SYSTEM.WPB |
| | AMEND. TO 2010 FBC SEC. 107.3.5.1.3. |
| | 2) SHT. P2.1.2 - THERE IS A 4" RAIN WATER LEADER IN THE |
| | PARTS AREA 3 135 THAT TERMINATES NOWHERE. CLARIFY. |
| | 3) SHT. P5.1 - SIZE THE VENT FOR THE HANDICAP WATER |
| | CLOSET IN THE MEN'S RESTROOM # 112. |
| | 4) THE 3" VTR'S FOR THE SHOWROOM AND SERVICE AREA |
| | REDUCE FROM 3" TO 2" .CLARIFY. |
| | 5) SHT.P2.1.1 REFERS TO 1" CONDENSATE PIPE AND PUMP |
| | ABOVE CEILING BUT NOTHING IS SHOWN. CLARIFY. |
| | 6) SHT. P2.1.2 - SHOWS A 4" RAINWATER LINE WITH NO |
| | TERMINATION POINT AND ALSO SHOWS A 4" RAINWATER LEADER |
| | WITH 870 SQ. FT. WITH NO TERMINATION POINT.SEE PARTS |
| | AREA PLAN.CLARIFY. |
| | 7) SUBMIT A CONDENSATE RISER DIAGRAM. SHOW ALL PIPE |
| | SIZES. WPB AMEND. TO 2010 FBC SEC.107.2.1. |
| | 8) SHT. P2.1.2 - THERE IS A CONDENSATE BRANCH NEAR THE |
| | EXTERIOR WALL IN THE SERVICE ARE BY GRID LINE 5F THAT |
| | GOES NOWHERE. CLARIFY. |
| | 9) SUBMIT A REVISED RAINWATER RISER DIAGRAM THAT |
| | CLEARLY REFLECTS ALL THE CHANGES TO THE STORWATER |
| | PIPING SYSTEM.WPB AMEND. TO 2010 FBC SEC.107.3.5.1.3. |
| | 10) SHT.P2.1.2 - SIZE THE CONDENSATE LINE EXITING THE |
| | BUILDING . |
| | 11) SHT.P2.1.3 - INDICATE THE TYPE OF PIPING BEING |
| | UTILIZED FOR THE COMPRESSED AIR SYSTEM. PVC IS NOT |
| | APPROVED TO BE USED FOR COMPRESSED AIR. |
| | 12) SHT.P2.1.3 - THE UNDERGROUND COMPRESSED AIR AND THE |
| | WATER LINES ARE NOT SHOWN CONTINUING ON SHT. P2.1.2. |
| | CLARIFY. |
| | 13) SHT. P2.1.3 - SHOWS A 1" COMPRESSED AIR LINE |
| | ENTERING AN AREA THAT COULD BE THE COMRESSOR ROOM # |
| | 143. IF SO, IDENTIFY THE LINE AS SUCH. |
| | 14) SHT. P2.1.2 - LOCATION OF EYEWASH AT EQUIPMENT |
| | STORAGE AREA # 145 SHOWN ON RISER DOES NOT CORRELATE |
| | WITH THE RSANITARY TISER ON SHT.P5.1. |
| | 15) SHT.P2.1.2 - SHOWS A 3" RAINWATER LEADER IN STAIR |
| | ENCLOSURE # 3. PENETRATIONS INTO AND OPENINGS THROUGH |
| | AN EXIT ENCLOSURE ARE PROHIBITED EXCEPT AS PROVIDED IN |
| | 2010 FBC SEC.1022.4. |
| | 16) SUPPLY CONFIRMATION FROM SCHIER PRODUCTS THAT THE |
| | OIL/SAND CALCULATIONS HAVE BEEN REVIEWED AND THAT THE |
| | SIZE OF THE INTERCEPTOR IS SIZED PROPERLY.2010 FPC |
| | SEC.1003.2. YOU CAN CONTACT LEE SCHNEEWEISS AT |
| | 1-800-538-4792 & [email protected]. I HAVE CALCULATED |
| | THE SQUARE FOOTAGE OF THIS AREA FROM SHT.A114 AND THE |
| | RESULT I HAVE IS APPROXIMATELY 1900 SQ. FEET WHICH IS |
| | HIHER THAN YOUR CALCULATIONS. |
| | 17.) SUBMIT SPECIFICATIONS FOR THE AIR COMPRESSORS. WPB |
| | AMEND. TO 2010 FBC SEC.107.2.1. |
| | 18) SHT.P3.1.2 - THE NUMBER OF COMPRESSED AIR OULETS DO |
| | NOT CORRELATE WITH SHT.P6.1. THERE ARE 2 ADDITIONAL |
| | OUTLETS ON THE COMPRESSED AIR RISER. CLARIFY. |
| | 19) SHT. P5.1 - THE HANDICAPPPED LAVATORY IN THE MEN'S |
| | RESTROOM #141 IS NOT SHOWN ON THE SANITARY RISER. |
| | CLARIFY. |
| | 20) SHT. P6.1 - THE WATER RISER ON P6.1 DOES NOT |
| | CORRELATE WITH SHT.P3.1.2. ( SERVICE AREA DOMESTIC |
| | WATER PLAN ) CLARIFY. |
| | 21) SHT.P6.1 - WATER RISER - THE NUMBER OF HOSE BIBBS, |
| | THE LAYOUT OF THE HOSE BIBBS, WHERE THE WATER MAUN |
| | ENTERS THE BUILDING DOES NOT SEEM TO CORRELATE WITH |
| | SHT. P3.1.2. |
| | 22) SHT. P6.1 SHOWS AN 1 1/2" LINE TO SK-2. IS THIS |
| | CORRECT? |
| | 23) SHT. P6.1 - THE WATER LINE GOES FROM 2 1/2" TO 2" |
| | THEN BACK TO 2 1/2" AGAIN. CLARIFY. SEE AREA AT MEN'S |
| | RESTROOM #112. |
| | |
| | PLUMBING PLAN REVIEW |
| | TIM LARGE |
| | CHIEF PLUMBING INSPECTOR |
| | 561-805-6692 |
| | [email protected] |
| | |
| | |
| | |
| | |
| | |
| | |
| | |