| Date |
Text |
| 2015-01-29 06:10:33 | 1) TRENCH DRAINS SHALL COMPLY WITH ASME 112.6.3 PER THE |
| | 2010 FL. PLBG. CODE SEC.412.1. SUBMIT DOCUMENTATION TO |
| | SHOW COMPLIANCE. |
| | 2) SHT.P2.1.2. HAS ARROWS INDICATING AN UNDERGROUND |
| | STORM DRAIN BUT NO PIPING IS SHOWN ON THE PLAN.SUBMIT |
| | DRAWINGS THAT CLEARLY REFLECT THE PIPING AND THE SCOPE |
| | OF WORK TO BE DONE. WPB AMEND. TO 2010 FBC SEC.107.2.1. |
| | 3) THE CONDENSATE LINES ON THE PLAN ARE VERY LIGHT AND |
| | DIFFICULT TO READ. THESE WILL NOT SHOW WHEN THE PLANS |
| | ARE SCANNED FOR RECORD RETENTION. THE CONDENSATE LINES |
| | AND ALL OTHER PIPING ON THE PLUMBING PLANS SHALL BE |
| | CLEAR IN DETAIL AND LEGIBLE. WPB AMEND. TO 2010 FBC |
| | SEC.107.2.1. |
| | 4) SHT.P2.1.2. - SHOWS P-TRAPS ON CONDENSATE LINES BUT |
| | THE PLAN DOES NOT SHOW TO WHAT THEY ARE CONNECTED. |
| | CLARIFY. |
| | 5) THERE ARE NOTES & ARROWS ALL OVER THE PLANS ( |
| | P2.1.2, P2.1.3, P3.1.2) IDENTIFYING ITEMS BUT NOTHING |
| | IS SHOWN AT THE LOCATION,E.G. STORM DRAIN LINE, RAIN |
| | WATER LEADERS, 4" STORM DRAIN LINE, BFP DEVICE, 3" VENT |
| | BELOW GRADE, ETC. WPB AMEND. TO FBC SEC. 107.2.1. |
| | 6) SHT. P2.1.3 - CALLS OUT A 4" SANITARY LINE |
| | DISCHARGING INTO THE OIL/SAND SEPARATOR. WHAT |
| | DISCHARGES INTO THIS LINE? SANITARY LINES SHALL NOT |
| | DISCHARGE INTO THE SEPARATOR. WASTES THAT DO NOT |
| | REQUIRE TREATMENT OR SEPARATION SHALL NOT BE DISCHARGED |
| | INTO ANY INTERCEPTOR OR SEPARATOR. 2010 1003.2. PLANS |
| | REFER TO "BROADWAY EQUIPMENT PLANS." CLARIFY. |
| | 7) INDICATE THE TYPE OF PIPE MATERIAL BEING USED FOR |
| | THE COMPRESSED AIR SYSTEM. PVC PIPING CANNOT BE USED |
| | FOR COMPRESSED AIR PER MANUFACTURER'S SPECIFICATIONS. |
| | FPC SEC.303.2 |
| | 8) SHT.P2.1.3 - CLEANOUTS SHALL BE INSTALLED IN THE |
| | TRENCH DRAIN SYSTEM PER THE 2010 FPC SEC. 708. |
| | 9) CLEARLY IDENTIFY ALL PIPE LINES ON THE PLANS, AND |
| | SIZE ALL LINES. WPB AMEND. TO 2010 FBC SEC.107.2.1. |
| | 10) SHT.P5.1 - THERE ARE LINES INTO THE INTERCEPTOR |
| | THAT HAVE NO BEGINNING POINT ( 3" & 4" LINES). CLARIFY. |
| | 11) SHT. P5.1 - A LAVATORY IN THE WOMEN'S RESTROOM IS |
| | MISSING FROM THE SANITARY RISER FOR THE SERVICE AREA.. |
| | 12) SHT. P6.1 - THE DOMESTIC WATER RISER IS SO LIGHT ON |
| | THE PLANS IT IS ILLEGIBLE. SUBMIT CLEAR AND LEGIBLE |
| | DRAWINGS THE REFLECT THE SCOPE OF WORK.WPB AMEND. TO |
| | 2010 FBC SEC.107.2.1. |
| | 13) SHT. P6.1 - THE COMPRESSED AIR RISER IS SO LIGHT ON |
| | THE PLANS IT IS ILLEGIBLE. SUBMIT CLEAR AND LEGIBLE |
| | DRAWINGS THE REFLECT THE SCOPE OF WORK.WPB AMEND. TO |
| | 2010 FBC SEC.107.2.1. |
| | 14) SHT. P5.1 - THERE IS A LAVATORY MISSING ON THE |
| | SERVICE AREA SANITARY RISER. |
| | 15) THE SANITARY PIPING FOR THE EMERGENCY |
| | EYEWASH/SHOWER ON THE RISER DOES NOT CORRELATE WITH THE |
| | FLOOR PLAN. CLARIFY. |
| | 16) THE WASTE LINES SHOWN ON THE RISER BY THE OIL/SAND |
| | SEPARATOR ARE NOT SHOWN ON SHT. P2.1.2.CLARIFY. |
| | 17) PLEASE ASSEMBLE THE PLANS INTO TWO COMPLETE SETS OF |
| | PLANS WITH THE SHEETS BOUND TOGETHER. |
| | |
| | PLUMBING PLAN REVIEW |
| | TIM LARGE |
| | CHIEF PLUMBING INSPECTOR |
| | 561-805-6692 |
| | [email protected] |
| | |
| | |