| Date |
Text |
| 2015-04-25 06:38:12 | BUILDING PLAN REVIEW |
| | PERMIT: 15010402 |
| | ADD: 255 EVERNIA ST # 1405 |
| | CONT: BLUEWATER BUILDERS |
| | TEL: (954)753-7233 |
| | |
| | 2010 FLORIDA BUILDING CODE W |
| | * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION |
| | 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. |
| | |
| | 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| | OF THE FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 2ND REVIEW |
| | DATE: SAT. APRIL 25/ 2015 |
| | ACTION: DENIED |
| | |
| | NOTICE!!!!!! WHEN RESUBMITTING PLANS PLEASE INDICATE |
| | THE REVISION & REMOVE ANY VOIDED SHEETS & REPLACE ANY |
| | PAGES AS NECESSARY. A TRANSMITTAL LETTER LISTING THE |
| | ORIGINAL REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF |
| | THE REVISION MADE, IDENTIFYING THE SHEET OR |
| | SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND WILL |
| | HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR |
| | ANTICIPATED COOPERATION. |
| | |
| | |
| | NOTICE: SUBMIT TEST REPORTS TO THE DESIGNER OF RECORD |
| | FOR REVIEW BEFORE SUBMITTAL TO THE BUILDING DEPARTMENT. |
| | |
| | 1) 2ND REQUEST, SUPPLY THE ASTM E-90 TEST REPORT FOR |
| | FLOOR INSULATION. SHEET A152 SHOWS AN EXISTING SINGLE |
| | ENTRY, SHEET A201 SHOWS A NEW PORTION OF THE CORRIDOR, |
| | A LOBBY AREA AND 2 NEW ENTRIES TO (2) NEW R2 UNITS. THE |
| | PLANS INDICATE EITHER A WALL IDENTIFICATION TAG 1 OR 2. |
| | SHEET A903 SHOWS BOTH WALLS AS 1 HOUR FIRE RATED WALLS, |
| | BOTH DETAILS ARE MISSING COMPLIANCE WITH: |
| | 2010 FBC-B 1207.2 AIR-BORNE SOUND. |
| | WALLS, PARTITIONS AND FLOOR/CEILING ASSEMBLIES |
| | SEPARATING DWELLING UNITS FROM EACH OTHER OR FROM |
| | PUBLIC OR SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION |
| | CLASS (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) |
| | FOR AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM |
| | E 90. PENETRATIONS OR OPENINGS IN CONSTRUCTION |
| | ASSEMBLIES FOR PIPING; ELECTRICAL DEVICES; RECESSED |
| | CABINETS; BATHTUBS; SOFFITS; OR HEATING, VENTILATING OR |
| | EXHAUST DUCTS SHALL BE SEALED, LINED, INSULATED OR |
| | OTHERWISE TREATED TO MAINTAIN THE REQUIRED RATINGS. |
| | THIS REQUIREMENT SHALL NOT APPLY TO DWELLING UNIT |
| | ENTRANCE DOORS; HOWEVER, SUCH DOORS SHALL BE TIGHT |
| | FITTING TO THE FRAME AND SILL. |
| | |
| | 2) 2ND REQUEST, SUPPLY THE ASTM E-90 TEST REPORT FOR |
| | FLOOR INSULATION. SHEET A152 NOTE # 3 INDICATES TO |
| | REMOVE ALL FLOOR TILE AND GROUT. SHEET A202 SHOW NEW |
| | FLOOR TILE BUT THERE IS NO NOTES ABOUT THE FLOOR |
| | FINISHES. PLEAS PROVIDE COMPLIANCE WITH : |
| | 2010 FBC-B 1207.3 STRUCTURE-BORNE SOUND. |
| | FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR |
| | BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA |
| | WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION |
| | CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD |
| | TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E 492. |
| | |
| | 3) 2ND REQUEST SUPPLY THE TEST REPORT FOR FLAME SPREAD. |
| | 2010 FBC-B 603.2.EXCEPTION (2) INSULATION INSTALLED |
| | BETWEEN A FINISHED FLOOR AND SOLID DECKING WITHOUT |
| | INTERVENING AIRSPACE SHALL BE ALLOWED TO HAVE A FLAME |
| | SPREAD INDEX OF NOT MORE THAN 200. |
| | |
| | 4) COMPLIED. |
| | |
| | JAMES A. WITMER CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | TEL: 561-805-6715 |
| | FAX: 561-805-6676 |