| 2015-04-25 06:31:41 | BUILDING PLAN REVIEW |
| | PERMIT: 15010400 |
| | ADD: 255 EVERNIA ST # 1404 |
| | CONT: BLUEWATER BUILDERS |
| | TEL: (954)753-7233 |
| | |
| | 2010 FLORIDA BUILDING CODE W |
| | * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION |
| | 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. |
| | |
| | 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| | OF THE FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 2ND REVIEW |
| | DATE: SAT. APRIL 25/ 2015 |
| | ACTION: DENIED |
| | |
| | NOTICE!!!!!!WHEN RESUBMITTING PLANS PLEASE INDICATE THE |
| | REVISION & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES |
| | AS NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |
| | NOTICE: SUBMIT TEST REPORTS TO THE DESIGNER OF RECORD |
| | FOR REVIEW BEFORE SUBMITTAL TO THE BUILDING DEPARTMENT. |
| | |
| | |
| | 1) 2ND REVIEW, PROVIDE ACTUAL TEST IN COMPLIANCE WITH |
| | ASTM E 90 FOR FLOOR INSULATION. SHEET A152 SHOWS AN |
| | EXISTING SINGLE ENTRY, SHEET A201 SHOWS A NEW PORTION |
| | OF THE CORRIDOR, A LOBBY AREA AND 2 NEW ENTRIES TO (2) |
| | NEW R2 UNITS. THE PLANS INDICATE EITHER A WALL |
| | IDENTIFICATION TAG 1 OR 2. SHEET A903 SHOWS BOTH WALLS |
| | AS 1 HOUR FIRE RATED WALLS, BOTH DETAILS ARE MISSING |
| | COMPLIANCE WITH: |
| | 2010 FBC-B 1207.2 AIR-BORNE SOUND. |
| | WALLS, PARTITIONS AND FLOOR/CEILING ASSEMBLIES |
| | SEPARATING DWELLING UNITS FROM EACH OTHER OR FROM |
| | PUBLIC OR SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION |
| | CLASS (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) |
| | FOR AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM |
| | E 90. PENETRATIONS OR OPENINGS IN CONSTRUCTION |
| | ASSEMBLIES FOR PIPING; ELECTRICAL DEVICES; RECESSED |
| | CABINETS; BATHTUBS; SOFFITS; OR HEATING, VENTILATING OR |
| | EXHAUST DUCTS SHALL BE SEALED, LINED, INSULATED OR |
| | OTHERWISE TREATED TO MAINTAIN THE REQUIRED RATINGS. |
| | THIS REQUIREMENT SHALL NOT APPLY TO DWELLING UNIT |
| | ENTRANCE DOORS; HOWEVER, SUCH DOORS SHALL BE TIGHT |
| | FITTING TO THE FRAME AND SILL. |
| | |
| | 2) 2ND REVIEW, PROVIDE ACTUAL TEST IN COMPLIANCE WITH |
| | ASTM E 90 FOR FLOOR INSULATION. SHEET A152 NOTE # 3 |
| | INDICATES TO REMOVE ALL FLOOR TILE AND GROUT. SHEET |
| | A202 SHOW NEW FLOOR TILE BUT THERE IS NO NOTES ABOUT |
| | THE FLOOR FINISHES. PLEASE PROVIDE COMPLIANCE WITH : |
| | 2010 FBC-B 1207.3 STRUCTURE-BORNE SOUND. |
| | FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR |
| | BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA |
| | WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION |
| | CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD |
| | TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E 492. |
| | |
| | 3) 2ND REVIEW, PROVIDE ACTUAL TEST IN COMPLIANCE WITH |
| | ASTM E 90 FOR FLOOR INSULATION. 2010 FBC-B |
| | 603.2.EXCEPTION (2) INSULATION INSTALLED BETWEEN A |
| | FINISHED FLOOR AND SOLID DECKING WITHOUT INTERVENING |
| | AIRSPACE SHALL BE ALLOWED TO HAVE A FLAME SPREAD INDEX |
| | OF NOT MORE THAN 200. |
| | |
| | 4) COMPLIED. |
| | |
| | |
| | JAMES A. WITMER CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | TEL: 561-805-6715 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |