| 2015-01-15 07:15:09 | 1/15/2015 |
| | PROJECT: 308 ARLINGTON RD. DOCK PEDISTAL |
| | PERMIT#: 15010385 |
| | CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC |
| | ,2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1, |
| | ADMINISTRATION, 2012 FBC SUPPLEMENTS. |
| | 1ST ELECTRICAL PLAN REVIEW |
| | ACTION: DENIED |
| | |
| | 1) PROVIDE A SITE PLAN FOR ADDITIONAL INFORMATION |
| | INDICATING THE SOURCE OF THE CIRCUIT THAT IS BEING |
| | EXTENDED TO THE PEDISTAL, THE LOCATION OF THE PEDISTAL |
| | RELATIVE TO THE EXISTING JUNCTION BOX AND THE ORIGINAL |
| | SOURCE. FBC 107.3.2 |
| | |
| | 2) PROVIDE ADDITIONAL INFORMATION RELATING TO THE |
| | CIRCUIT IN THE EXISTING JUNCTION BOX. IS IT AN EXISTING |
| | CIRCUIT THAT HAS BEEN ABANDONED AND NO LONGER HAS ANY |
| | LOAD CONNECTED TO IT? OR IS THE PROPOSED EXTENDED |
| | CIRCUIT FOR THE NEW DOCK PEDISTAL PROPOSED TO BE |
| | CONNECTED AN EXISTING LIVE LOAD? |
| | |
| | 3) PROVIDE MANUFACTURER DOCUMENTATION ON THE PROPOSED |
| | DOCK PEDISTAL TO INDICATE THE MINIMUM MANUFACTURER |
| | RECOMENDED CIRCUITRY REQUIRED AND COMPLIANCE WITH NEC |
| | 110.3(B) LISTING WITH A NRTL |
| | |
| | 4) PROVIDE A LOAD CALCULATION INDICATING THE |
| | AVIALABILITY OF THE REQUIRED AMPACITY FOR THE NEW DOCK |
| | POWER PEDISTAL. NEC 220.14(C) |
| | |
| | 5) .PROVIDE A PANEL SCHEDULE TO INDICATE THE SOURCE |
| | BREAKER. EVERY CIRCUIT AND CIRCUIT MODIFICATION SHALL |
| | BE LEGIBLY IDENTIFIED AS TO ITS CLEAR, EVIDENT, AND |
| | SPECIFIC PURPOSE OR USE. NEC 408.4 |
| | |
| | 6) ALL INFORMATION, DRAWINGS, SPECIFICATIONS AND |
| | ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE OF |
| | THE PERSON RESPONSIBLE FOR THE DESIGN. FL SS 471, |
| | 668.001-668.006 FBC, WPB AMENDMENTS 107.2.1 |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. SEE LINK: |
| | HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/ |
| | 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF |
| | |
| | ADDITIONALLY, IT IS REQUIRED TO INSERT THE CORRECTED |
| | PAGES INTO THE DENIED SUBMITTAL PACKAGE. VOID THE |
| | PREVIOUSLY REVIEWED SHEETS AND LEAVE FOR COMPARATIVE |
| | REVIEW. |
| | |
| | DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421, |
| | 561-805-6717 OR [email protected] |
| | |
| | |
| | |
| | |
| | |
| | |