| Notes |
| Date |
Text |
| 2015-01-24 09:34:26 | 1) SHT.A1.1 - FINISH SCHEDULE - INDICATES THE WALLS IN | | | THE MEN'S AND WOMEN'S RESTROOM TO BE PAINTED. PER THE | | | 2010 FBC SEC.1210.2, WALLS AND PARTITIONS WITHIN 2 FEET | | | OF URINALS AND WATER CLOSETS SHALL HAVE A SMOOTH,HARD, | | | NONABSORBENT SURFACE TO A HEIGHT OF 4 FEET ABOVE THE | | | FLOOR AND THE MATERIAL SHALL BE OF A TYPE THAT IS NOT | | | ADVERSELY AFFECTED BY MOISTURE. | | | 2) SHT. A2.1 - THE HEIGHT OF THE GRAB BARS SHALL BE | | | MEASURED TO THE TOP OF THE GRIPPING SURFACE, NOT TO THE | | | CENTER LINE AS SHOWN. 2010 FAC SEC.609.4. | | | 3) SHT. P1.1 REFERS TO SHT. P0.1 FOR THE WATER HEATER | | | DETAI. THERE IS NO SUCH SHEET IN THE PLANS. PROVIDE A | | | DETAIL FOR THE WATER HEATER. THE WATER HEATER SHALL BE | | | EQUIPPED WITH A PAN AND A PAN DRAIN INSTALLED IN | | | ACCORDANCE WITH THE 2010 FPC SEC.504.7. | | | | | | PLUMBING PLAN REVIEW | | | TIM LARGE | | | CHIEF PLUMBING INSPECTOR | | | 561-805-6692 | | | [email protected] | | | |
|