| 2015-01-26 09:48:05 | BUILDING PLAN REVIEW | | | REVISION: 15010345 | | | PERMIT: 14081143 | | | ADD: 303 BANYAN ST. # 101 | | | CONT: FISHER | | | TEL: (561)691-4716 | | | | | | 2010 FLORIDA BUILDING CODE W | | | * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA | | | BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION | | | 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. | | | | | | 2010 EXISTING BUILDING CODE LEVEL II 701.3 | | | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, | | | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS | | | OF THE FLORIDA BUILDING CODE, BUILDING. | | | | | | 1ST REVIEW | | | DATE: MON. JAN 26/ 2015 | | | ACTION: DENIED | | | | | | 1) SHEET A1.1 THE ROOM FINISH SCHEDULE INDICATES | | | PAINTED WALLS FOR RESTROOMS, PLEASE PROVIDE COMPLIANCE | | | WITH 2010 FBC-B 1210.2 | | | WALLS AND PARTITIONS. | | | WALLS AND PARTITIONS WITHIN 2 FEET (610 MM) OF URINALS | | | AND WATER CLOSETS SHALL HAVE A SMOOTH, HARD, | | | NONABSORBENT SURFACE, TO A HEIGHT OF 4 FEET (1219 MM) | | | ABOVE THE FLOOR, AND EXCEPT FOR STRUCTURAL ELEMENTS, | | | THE MATERIALS USED IN SUCH WALLS SHALL BE OF A TYPE | | | THAT IS NOT ADVERSELY AFFECTED BY MOISTURE. | | | | | | 2) SHEET A2.1 DETAIL 08 THE INSWING DOOR HAS ONLY 12 | | | INCHES FROM LATCH SIDE OF DOOR TO WALL, THE 2010 FL | | | ACCESSIBILITY CODE FIGURE 404.2.4.1 REQUIRES 18 INCHES. | | | | | | JAMES A. WITMER CBO | | | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER | | | TEL: 561-805-6715 | | | FAX: 561-805-6676 | | | E-MAIL: [email protected] | | | |
|