| Date |
Text |
| 2015-01-23 15:23:38 | BUILDING PLAN REVIEW |
| | PERMIT: 15010290 |
| | ADD: 1640 CLARE AVE. |
| | CONT: THE WEITZ CO. |
| | TEL: (561)684-4807 |
| | |
| | 2010 FLORIDA BUILDING CODE W |
| | * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION |
| | 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. |
| | |
| | 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| | OF THE FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | DATE: FRI. JAN. 23/ 2015 |
| | ACTION: DENIED |
| | |
| | 1) SHEET A101; MISSING CRITERIA FOR COMMERCIAL BUILDING |
| | PLAN REVIEW: |
| | 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING |
| | CODE, CHAPTER 1, ADMINISTRATION: |
| | 107.3.5 MINIMUM PLAN REVIEW CRITERIA FOR BUILDINGS. |
| | 1.1) TYPE OF OCCUPANCY |
| | 1.2) MINIMUM BUILDING TYPE |
| | 1.3) FIRE SPRINKLERED OR NOT? |
| | 1.4) OCCUPANCY LOAD/EGRESS REQUIREMENTS SHALL INCLUDE: |
| | OCCUPANCY LOAD |
| | GROSS |
| | NET |
| | MEANS OF EGRESS PROVIDE A LIFE SAFETY PLAN SHOWING ALL |
| | RACK STORAGE, IS THIS HIGH RACK STORAGE |
| | EXIT ACCESS |
| | EXIT |
| | EXIT DISCHARGE |
| | 2) SHEET A102 SHOWS A NEW OFFICE ENCLOSURE, IT APPEARS |
| | TO BE AN ACCESSORY OCCUPANCY <10% OF THE FLOOR AREA : |
| | 2.1 THE PLANS DO NOT INDICATE THE WALL TYPE OF |
| | CONSTRUCTION, IF THERE IS TO BE A CEILING, HOW THE |
| | CEILING IS TO BE HUNG NOR IF THERE IS GOING TO BE |
| | CEILING JIOST? IS THERE TO BE STORAGE ABOVE THE OFFICE |
| | AREA, MEZZANINE? 107.2.1.3 ADDITIONAL INFORMATION IS |
| | REQUIRED. |
| | |
| | 3) THE PLANS DO NOT INDICATE IF THERE IS TO BE |
| | MECHANICAL VENTILATION, PLEASE PROVIDE COMPLIANCE WITH |
| | 2010 FBC-B 1203.1 GENERAL. |
| | BUILDINGS SHALL BE PROVIDED WITH NATURAL VENTILATION IN |
| | ACCORDANCE WITH SECTION 1203.4, OR MECHANICAL |
| | VENTILATION IN ACCORDANCE WITH THE FLORIDA BUILDING |
| | CODE, MECHANICAL. |
| | |
| | 4A) IF HIS SPACE IS TO BE AIR CONDITIONED PLEASE |
| | PROVIDE INSULATION IN ACCORDANCE WITH THE FL. ENERGY |
| | CODE. FBC-ENERGY 502.2.2.1.1 ABOVE-GRADE WALLS. |
| | THE MINIMUM THERMAL RESISTANCE (R-VALUE) OF THE |
| | INSULATING MATERIAL(S) INSTALLED IN THE WALL CAVITY |
| | BETWEEN THE FRAMING MEMBERS AND CONTINUOUSLY ON THE |
| | WALLS SHALL BE AS SPECIFIED IN TABLE 502.1.1.1(1) OR |
| | TABLE 502.1.1.1(2), BASED ON FRAMING TYPE AND |
| | CONSTRUCTION MATERIALS USED IN THE WALL ASSEMBLY. THE |
| | R-VALUE OF INTEGRAL INSULATION INSTALLED IN CONCRETE |
| | MASONRY UNITS (CMU) SHALL NOT BE USED IN DETERMINING |
| | COMPLIANCE WITH TABLE 502.1.1.1(1) OR TABLE |
| | 502.1.1.1(2). |
| | |
| | 4B) 502.2.1.2 CEILING INSULATION. INSULATION INSTALLED |
| | ON A SUSPENDED CEILING WITH REMOVABLE CEILING TILES |
| | SHALL NOT BE CONSIDERED PART OF THE MINIMUM THERMAL |
| | RESISTANCE OF THE ROOF INSULATION UNLESS THE |
| | ROOF/CEILING CAVITY IS SEALED FROM THE EXTERIOR |
| | ENVIRONMENT. |
| | |
| | 5) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION |
| | & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |
| | A THOROUGH REVIEW CAN NOT BE MADE AT THIS TIME, AS A |
| | RESULT OF THE ADDITIONAL INFORMATION REQUESTED |
| | ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF |
| | THIS REVIEW. |
| | |
| | JAMES A. WITMER CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | TEL: 561-805-6715 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |
| | |
| | |