| 2015-01-14 08:07:12 | BUILDING PROVISO: |
| | BUILDING APPROVED WITH EXCEPTION! |
| | THIS PLAN HAS BEEN APPROVED PROVISIONALLY. FAILURE TO |
| | CORRECT THE LISTED DEFICIENCIES IN THIS PLAN PRIOR TO |
| | INSPECTION WILL RESULT IN FAILED INSPECTION(S) AND THE |
| | ASSESSMENT OF RE-INSPECTION FEE(S). REVISIONS REQUIRE |
| | ADDITIONAL REVIEWS WITH ASSOCIATED FEES. |
| | |
| | ONLY ONE MEANS OF EGRESS IS REQUIRED, OCCUPANT LOAD NOR |
| | TRAVEL DISTANCE REQUIRES A 2ND EXIT, SINCE THE DESIGNER |
| | OF RECORD HAS ELECTED FOR A 2ND MEANS OF EGRESS THROUGH |
| | THE STOCK ROOM, PLEASE SUBMIT A REVISION MEETING THESE |
| | CODE REQUIREMENTS: |
| | |
| | 2010 FBC-B 1014.2 EGRESS THROUGH INTERVENING SPACES. |
| | EGRESS THROUGH INTERVENING SPACES SHALL COMPLY WITH |
| | THIS SECTION. |
| | 4. EGRESS SHALL NOT PASS THROUGH KITCHENS, STORAGE |
| | ROOMS, CLOSETS OR SPACES USED FOR SIMILAR PURPOSES. |
| | EXCEPTIONS: |
| | 2. MEANS OF EGRESS ARE NOT PROHIBITED THROUGH |
| | STOCKROOMS IN GROUP M OCCUPANCIES WHEN ALL OF THE |
| | FOLLOWING ARE MET: |
| | 2.1. THE STOCK IS OF THE SAME HAZARD CLASSIFICATION AS |
| | THAT FOUND IN THE MAIN RETAIL AREA; |
| | 2.2. NOT MORE THAN 50 PERCENT OF THE EXIT ACCESS IS |
| | THROUGH THE STOCKROOM; |
| | 2.3. THE STOCKROOM IS NOT SUBJECT TO LOCKING FROM THE |
| | EGRESS SIDE; AND |
| | 2.4. THERE IS A DEMARCATED, MINIMUM 44-INCH-WIDE (1118 |
| | MM) AISLE DEFINED BY FULL- OR PARTIAL-HEIGHT FIXED |
| | WALLS OR SIMILAR CONSTRUCTION THAT WILL MAINTAIN |
| | THE REQUIRED WIDTH AND LEAD DIRECTLY FROM THE RETAIL |
| | AREA TO THE EXIT WITHOUT OBSTRUCTIONS. |