Plan Review Notes
Plan Review Notes For Permit 15010288
Permit Number 15010288
Review Stop B
Sequence Number 1
Notes
Date Text
2015-01-14 08:07:12BUILDING PROVISO:
 BUILDING APPROVED WITH EXCEPTION!
 THIS PLAN HAS BEEN APPROVED PROVISIONALLY. FAILURE TO
 CORRECT THE LISTED DEFICIENCIES IN THIS PLAN PRIOR TO
 INSPECTION WILL RESULT IN FAILED INSPECTION(S) AND THE
 ASSESSMENT OF RE-INSPECTION FEE(S). REVISIONS REQUIRE
 ADDITIONAL REVIEWS WITH ASSOCIATED FEES.
  
 ONLY ONE MEANS OF EGRESS IS REQUIRED, OCCUPANT LOAD NOR
 TRAVEL DISTANCE REQUIRES A 2ND EXIT, SINCE THE DESIGNER
 OF RECORD HAS ELECTED FOR A 2ND MEANS OF EGRESS THROUGH
 THE STOCK ROOM, PLEASE SUBMIT A REVISION MEETING THESE
 CODE REQUIREMENTS:
  
 2010 FBC-B 1014.2 EGRESS THROUGH INTERVENING SPACES.
 EGRESS THROUGH INTERVENING SPACES SHALL COMPLY WITH
 THIS SECTION.
 4. EGRESS SHALL NOT PASS THROUGH KITCHENS, STORAGE
 ROOMS, CLOSETS OR SPACES USED FOR SIMILAR PURPOSES.
 EXCEPTIONS:
 2. MEANS OF EGRESS ARE NOT PROHIBITED THROUGH
 STOCKROOMS IN GROUP M OCCUPANCIES WHEN ALL OF THE
 FOLLOWING ARE MET:
 2.1. THE STOCK IS OF THE SAME HAZARD CLASSIFICATION AS
 THAT FOUND IN THE MAIN RETAIL AREA;
 2.2. NOT MORE THAN 50 PERCENT OF THE EXIT ACCESS IS
 THROUGH THE STOCKROOM;
 2.3. THE STOCKROOM IS NOT SUBJECT TO LOCKING FROM THE
 EGRESS SIDE; AND
 2.4. THERE IS A DEMARCATED, MINIMUM 44-INCH-WIDE (1118
 MM) AISLE DEFINED BY FULL- OR PARTIAL-HEIGHT FIXED
 WALLS OR SIMILAR CONSTRUCTION THAT WILL MAINTAIN
 THE REQUIRED WIDTH AND LEAD DIRECTLY FROM THE RETAIL
 AREA TO THE EXIT WITHOUT OBSTRUCTIONS.